En-12
12
Heating capacity
shift *1
Normal mode
1
2
0
0
Save energy mode
0
1
High power mode 1
0
2
High power mode 2
0
3
Set this item when necessary.
13
(Forbidden)
1
3
0
0
(Factory default)
14
(Forbidden)
1
4
0
0
(Factory default)
16
(Forbidden)
1
6
0
0
(Factory default)
17
Height difference
between indoor
units
Standard
1
7
0
0
Forbidden
0
1
Height difference
0
2
Forbidden
0
3
Forbidden
0
4
If installing the indoor units (even only one set) to a lower floor than the outdoor unit, and
the height difference between the indoor units is 119 in (3 m) or greater (i.e., if installing
the indoor units on separate floors), set “02 (height difference)”.
20
Switching
between batch
stop or emergency
stop *1
Batch stop
2
0
0
0
Emergency stop
0
1
This mode selects the pattern of the stop function to be operated by the external input
terminal (CN134).
• Batch stop: The stop of all indoor units connected to same refrigerant system due to
input signal coming from CN134.
• Emergency stop: When emergency stop is actuated, the indoor unit does not accept
the operation command from the remote controller. On the other hand, when the emer-
gency stop is released (no input from CN134), the air conditioner does not return to the
original operation until the indoor unit is turned on by the remote controller.
21
Operation mode
selecting method
*1
Priority given to the first
command
2
1
0
0
Priority given to external input
of outdoor unit
0
1
Priority given to administrative
indoor unit
0
2
Select the priority setting of the operation mode.
• Priority given to the first command: Priority is given to the operation mode which is set first.
• Priority given to external input of outdoor unit: Priority is given to the operation mode
which is set by the external input terminal (CN132).
• Priority given to administrative indoor unit: Priority is given to the operation mode of the
administrative indoor unit which is set by the wired remote controller.
22
(Forbidden)
2
2
0
0
(Factory default)
23
(Forbidden)
2
3
0
0
(Factory default)
24
(Forbidden)
2
4
0
0
(Factory default)
25
(Forbidden)
2
5
0
0
(Factory default)
26
(Forbidden)
2
6
0
0
(Factory default)
27
(Forbidden)
2
7
0
0
(Factory default)
28
Change of unit
(Temperature)
Celsius (°C)
2
8
0
0
Fahrenheit (°F)
0
1
29
Change of unit
(Pressure)
Mpa
2
9
0
0
psi
0
1
30
Energy saving
level setting *1
Level 1 (stop)
3
0
0
0
Level 2
(operated at 40% capacity)
0
1
Level 3
(operated at 60% capacity)
0
2
Level 4
(operated at 80% capacity)
0
3
Level 5
(operated at 100% capacity)
0
4
The capacity limit can be selected by the external input terminal (CN133) when operat-
ing with the “Energy Saving Peak Cut function”.
The lower the level, the more the effect of energy saving, but the cooling/heating perfor-
mance will also drop.
31
(Forbidden)
3
1
0
0
(Factory default)
34
(Forbidden)
3
4
0
0
(Factory default)
35
Presence of
heater selection
control using
outdoor tempera-
ture *1
Invalid
3
5
0
0
Valid
0
1
If “Heater selection control 1 or 2 using outdoor temperature” is used for any of the
indoor units of the refrigerant system, select "Valid". For more details on settings for this
item , see the Design & Technical Manual.
36
Outdoor tempera-
ture zone bound-
ary temperature
A *1
-4.0°F (-20°C)
3
6
0
0
-0.4°F (-18°C)
0
1
3.2°F (-16°C)
0
2
6.8°F (-14°C)
0
3
10.4°F (-12°C)
0
4
14.0°F (-10°C)
0
5
17.6°F (-8°C)
0
6
21.2°F (-6°C)
0
7
24.8°F (-4°C)
0
8
For more details on settings for this item , see the Design & Technical Manual.
37
Outdoor tempera-
ture zone bound-
ary temperature
B *1
42.8°F (6°C)
3
7
0
0
14.0°F (-10°C)
0
1
17.6°F (-8°C)
0
2
21.2°F (-6°C)
0
3
24.8°F (-4°C)
0
4
28.4°F (-2°C)
0
5
32.0°F (0°C)
0
6
35.6°F (2°C)
0
7
39.2°F (4°C)
0
8
42.8°F (6°C)
0
9
46.4°F (8°C)
1
0
50.0°F (10°C)
1
1
53.6°F (12°C)
1
2
57.2°F (14°C)
1
3
60.8°F (16°C)
1
4
64.4°F (18°C)
1
5
For more details on settings for this item , see the Design & Technical Manual.
40
Capacity prior-
ity setting (in low
noise mode) *1
Off (quiet priority)
4
0
0
0
On (capacity priority)
0
1
If the cooling/heating performance becomes insufficient when the low noise mode is
set, it is possible to set “capacity priority” that automatically cancels the low noise mode
(once performance is restored, the mode will automatically return to the low noise
mode).
41
Low noise mode
setting *1
Off (Normal)
4
1
0
0
On (Low noise mode)
0
1
42
(Forbidden)
4
2
0
0
(Factory default)
60
(Forbidden)
6
0
0
0
(Factory default)
61
(Forbidden)
6
1
0
0
(Factory default)
70
Electricity meter
No. setting 1 *2
Setting number (x00)
7
0
0
0
Setting number (x01)
0
1
······
···
···
Setting number (x98)
9
8
Setting number (x99)
9
9
Set the ones digit and tens digit of the No. of the electricity meter connected to CN135.
71
Electricity meter
No. setting 2 *2
Setting number (0xx)
7
1
0
0
Setting number (1xx)
0
1
Setting number (2xx)
0
2
Set the hundreds digit of the No. of the electricity meter connected to CN135.
72
Electricity meter
pulse setting 1 *3
Setting number (xx00)
7
2
0
0
Setting number (xx01)
0
1
······
···
···
Setting number (xx98)
9
8
Setting number (xx99)
9
9
Set the ones digit and tens digit of the No. of the electricity meter pulse setting con-
nected to CN135.
73
Electricity meter
pulse setting 2 *3
Setting number (00xx)
7
3
0
0
Setting number (01xx)
0
1
······
···
···
Setting number (98xx)
9
8
Setting number (99xx)
9
9
Set the hundreds digit and thousands digit of the electricity meter pulse setting con-
nected to CN135.
90
(Forbidden)
9
0
0
0
(Factory default)
*1: Do not set this for outdoor units with Slave setting.
*2: When electricity meter No. is set to “000” and “201 to 299”, the pulses input to
CN135 become ineffective. Available setting number is "001" to "200"
*3: When the electricity meter pulse setting is set to “0000”, the pulses input to CN135
become ineffective. Available setting number is "0001" to "9999"
01_9380545187-02_IM_EN.indd 12
01_9380545187-02_IM_EN.indd 12
12/15/2016 3:40:15 PM
12/15/2016 3:40:15 PM