23. VARIOUS PROTECTIONS
(1). DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas
temperature.
AG*V09/ 12/ 14LAC
104°C
101°C
110°C
09/ 12LAC
14LAC
4.0A / 3.5A
5.0A / 4.5A
6.5A / 6.0A
4.5A / 4.0A
6.0A / 5.5A
8.5A / 8.0A
6.5A / 6.0A
8.0A / 7.5A
8.5A / 8.0A
9.5A / 9.0A
When the discharge temperature becomes higher than Temperature ,the compressor frequency
is decreased 20 Hz, and it continues to decrease the frequency for 20 Hz every 120 seconds until
the temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature ,the control of the control of the
compressor frequency is released.
When the discharge temperature becomes higher than Temperature ,the compressor is stopped
and the indoor unit LED starts blinking.
(Table 17 : Discharge Temperature Over Rise Prevension Control / Release Temperature)
Temperature
Temperature
Temperature
(2). CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds
the current limit velue that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
(Table 18 : Current Release Operation Value / Release Value)
[ Heating ]
[ Cooling / Dry ]
OT : Outdoor Temperature
OT : Outdoor Temperature
05-19
7.0A / 6.5A
9.0A / 8.5A
10.5A / 10.0A
13.0A / 12.5A
OT (Control / Release)
17°C
12°C
5°C
OT (Control / Release)
17°C
12°C
5°C
46°C
40°C
OT (Control / Release)
46°C
40°C
OT (Control / Release)
09/ 12LAC
14LAC
Summary of Contents for AG * V12LAC Series
Page 4: ...1 SPECIFICATIONS R410A FLOOR type INVERTER ...
Page 6: ...2 DIMENSIONS R410A FLOOR type INVERTER ...
Page 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A FLOOR type INVERTER ...
Page 11: ...4 CIRCUIT DIAGRAM R410A FLOOR type INVERTER ...
Page 12: ...CIRCUIT DIAGRAM Models AG V09LAC AO V09LAC AG V12LAC AO V12LAC 04 01 INDOOR UNIT OUTDOOR UNIT ...
Page 13: ...CIRCUIT DIAGRAM Models AG V14LAC AO V14LAC 04 02 INDOOR UNIT OUTDOOR UNIT ...
Page 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A FLOOR type INVERTER ...
Page 35: ...6 REFRIGERANT CAUTION R410A R410A FLOOR type INVERTER ...
Page 62: ...9 REPLACEMENT PARTS R410A FLOOR type INVERTER ...
Page 80: ...10 INSTALLATION MANUAL R410A FLOOR type INVERTER ...
Page 89: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2007 Printed in Japan ...