![Fujitsu AG * V12LAC Series Service Instruction Download Page 42](http://html.mh-extra.com/html/fujitsu/ag-v12lac-series/ag-v12lac-series_service-instruction_118098042.webp)
Summary of R407C and R410A characteristics
Pressure (Mpa) Temp ( C)
2.20
37.9
2.25
38.7
2.30
39.6
2.35
40.5
2.40
41.3
2.45
42.1
2.55
43.8
2.60
44.6
2.65
45.3
2.70
46.1
2.75
46.8
2.80
47.6
2.85
48.3
2.90
49.0
2.95
49.8
3.00
50.5
3.05
51.2
3.10
51.9
3.15
52.6
3.20
53.2
3.25
53.9
3.30
54.6
3.35
55.3
3.40
55.9
3.45
56.5
3.50
57.1
2.55
57.8
3.60
58.4
3.65
59.0
3.70
59.6
3.75
60.2
3.80
60.8
3.85
61.4
3.90
52.0
3.95
62.5
4.00
63.1
4.05
63.6
4.10
64.2
4.15
64.8
Temp ( C) Pressure (Mpa)
39
2.27
40
2.32
41
2.38
42
2.44
44
2.57
45
2.63
46
2.69
47
2.76
48
2.83
49
2.90
51
3.04
52
3.11
53
3.18
54
3.26
56
3.41
57
3.49
58
3.57
59
3.65
61
3.82
62
3.90
63
3.99
64
4.08
Desighed pressure of R410A refrigerant
< Pressure Temp >
Relation between R410A condensing temperature and saturated pressure.
< Temp Pressure >
Advantage
Disadvantage
Suitable for
R410A
higher system
performance
Near-Azeotropic
refrigerant
1.6 times higher
(difficult to design against
pressure resistance)
Small Air-Conditioners
pressure than R22
R407C
similar pressure as R22
(possible to design
large equipment)
Zeotropic refrigerant
(handle with care)
Large Air-Conditioners
*
06-07
Summary of Contents for AG * V12LAC Series
Page 4: ...1 SPECIFICATIONS R410A FLOOR type INVERTER ...
Page 6: ...2 DIMENSIONS R410A FLOOR type INVERTER ...
Page 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A FLOOR type INVERTER ...
Page 11: ...4 CIRCUIT DIAGRAM R410A FLOOR type INVERTER ...
Page 12: ...CIRCUIT DIAGRAM Models AG V09LAC AO V09LAC AG V12LAC AO V12LAC 04 01 INDOOR UNIT OUTDOOR UNIT ...
Page 13: ...CIRCUIT DIAGRAM Models AG V14LAC AO V14LAC 04 02 INDOOR UNIT OUTDOOR UNIT ...
Page 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A FLOOR type INVERTER ...
Page 35: ...6 REFRIGERANT CAUTION R410A R410A FLOOR type INVERTER ...
Page 62: ...9 REPLACEMENT PARTS R410A FLOOR type INVERTER ...
Page 80: ...10 INSTALLATION MANUAL R410A FLOOR type INVERTER ...
Page 89: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2007 Printed in Japan ...