21. AIR OUTLET SELECTION ( DAMPER CONTROL )
22. 10
°C HEAT OPERATION
05-18
(Fig.12)
In Heating mode
44°C
Indoor heat exchanger
temperature
Upper & Lower
air flow
Upper air flow
35°C
The 10°C HEAT operation functions by pressing 10°C HEAT button on the remote controller.
The 10°C HEAT operation is almost the same operation as below settings.
(3). How to set to blow out air from the upper air outlet only
Set the air outlet selection switch to
mode HEAT
setting temperature 10°C
louver position (refer to 7.LOUVER CONTROLL)
fan mode AUTO
After 48hours of 10°C HEAT operation without Monitor operation,
fan mode will be fixed at HIGH speed.
( Table 16 )
Summary of Contents for AG * V12LAC Series
Page 4: ...1 SPECIFICATIONS R410A FLOOR type INVERTER ...
Page 6: ...2 DIMENSIONS R410A FLOOR type INVERTER ...
Page 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A FLOOR type INVERTER ...
Page 11: ...4 CIRCUIT DIAGRAM R410A FLOOR type INVERTER ...
Page 12: ...CIRCUIT DIAGRAM Models AG V09LAC AO V09LAC AG V12LAC AO V12LAC 04 01 INDOOR UNIT OUTDOOR UNIT ...
Page 13: ...CIRCUIT DIAGRAM Models AG V14LAC AO V14LAC 04 02 INDOOR UNIT OUTDOOR UNIT ...
Page 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A FLOOR type INVERTER ...
Page 35: ...6 REFRIGERANT CAUTION R410A R410A FLOOR type INVERTER ...
Page 62: ...9 REPLACEMENT PARTS R410A FLOOR type INVERTER ...
Page 80: ...10 INSTALLATION MANUAL R410A FLOOR type INVERTER ...
Page 89: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2007 Printed in Japan ...