( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )
1. COOLING OPERATION
1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is 2°C higher than a set temperature, the compressor operation
frequency will attain to maximum performance.
minimum
frequency
air flow
maximum
frequency
maximum
frequency
Outside air Outside air
temperature temperature
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
( Table 1 : Compressor Frequency Range )
When the compressor operates for 30 minutes continuously at over the maximum frequency ,
the maximum frequency is changed from Maximum Frequency to Maximum Frequency .
05-01
E zone
F zone
10°C
0°C
12°C
2°C
AG*V09LAC
18Hz
18Hz
18Hz
80Hz
96Hz
70Hz
90Hz
58Hz
90Hz
AG*V12LAC
AG*V14LAC
Hi
Me
Lo
Quiet
A zone
96Hz
61Hz
51Hz
33Hz
96Hz
61Hz
51Hz
33Hz
51Hz
33Hz
B zone
C zone
96Hz
61Hz
Upper&
Lower
air flow
Upper
air flow
D zone
64Hz
42Hz
36Hz
27Hz
E zone
64Hz
42Hz
36Hz
27Hz
F zone
A zone
B zone
C zone
D zone
E zone
F zone
64Hz
42Hz
36Hz
27Hz
96Hz
61Hz
45Hz
33Hz
96Hz
61Hz
45Hz
33Hz
45Hz
33Hz
96Hz
61Hz
64Hz
36Hz
36Hz
27Hz
64Hz
36Hz
36Hz
27Hz
64Hz
36Hz
36Hz
27Hz
* When the room temperature is b2°C to -2.5°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Figure 1 based on the
fan speed mode and the outdoor temperature.
* If the room temperature is 2.5°C lower than a set temperature, the compressor will be
stopped.
Upper & Lower
Upper
Upper & Lower
Upper
AG*V09/ 12LAC
Hi
Me
Lo
Quiet
A zone
90Hz
45Hz
42Hz
30Hz
90Hz
45Hz
42Hz
30Hz
42Hz
30Hz
B zone
C zone
90Hz
45Hz
Upper&
Lower
air flow
Upper
air flow
D zone
58Hz
38Hz
34Hz
24Hz
E zone
58Hz
38Hz
34Hz
24Hz
F zone
A zone
B zone
C zone
D zone
E zone
F zone
58Hz
38Hz
34Hz
24Hz
90Hz
45Hz
34Hz
24Hz
90Hz
45Hz
34Hz
21Hz
34Hz
21Hz
90Hz
45Hz
58Hz
34Hz
30Hz
21Hz
54Hz
34Hz
30Hz
21Hz
54Hz
34Hz
30Hz
21Hz
AG*V14LAC
Summary of Contents for AG * V12LAC Series
Page 4: ...1 SPECIFICATIONS R410A FLOOR type INVERTER ...
Page 6: ...2 DIMENSIONS R410A FLOOR type INVERTER ...
Page 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A FLOOR type INVERTER ...
Page 11: ...4 CIRCUIT DIAGRAM R410A FLOOR type INVERTER ...
Page 12: ...CIRCUIT DIAGRAM Models AG V09LAC AO V09LAC AG V12LAC AO V12LAC 04 01 INDOOR UNIT OUTDOOR UNIT ...
Page 13: ...CIRCUIT DIAGRAM Models AG V14LAC AO V14LAC 04 02 INDOOR UNIT OUTDOOR UNIT ...
Page 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A FLOOR type INVERTER ...
Page 35: ...6 REFRIGERANT CAUTION R410A R410A FLOOR type INVERTER ...
Page 62: ...9 REPLACEMENT PARTS R410A FLOOR type INVERTER ...
Page 80: ...10 INSTALLATION MANUAL R410A FLOOR type INVERTER ...
Page 89: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2007 Printed in Japan ...