Indoor unit: 14,000 Btu/h
Cooling
Pipe length
m
2.5
5
10
15
20
25
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
15
—
—
—
0.955
0.937
0.922
10
—
—
0.974
0.962
0.945
0.930
5
—
0.992
0.982
0.970
0.952
0.937
2.5
0.996
0.996
0.986
0.974
0.956
0.941
0
1.000
1.000
0.990
0.978
0.960
0.945
Indoor unit is lower
than outdoor unit *2
-2.5
1.000
1.000
0.990
0.978
0.960
0.945
-5
—
1.000
0.990
0.978
0.960
0.945
-10
—
—
0.990
0.978
0.960
0.945
-15
—
—
—
0.978
0.960
0.945
Heating
Pipe length
m
2.5
5
10
15
20
25
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
15
—
—
—
0.972
0.945
0.919
10
—
—
0.992
0.972
0.945
0.919
5
—
1.000
0.992
0.972
0.945
0.919
2.5
1.000
1.000
0.992
0.972
0.945
0.919
0
1.000
1.000
0.992
0.972
0.945
0.919
Indoor unit is lower
than outdoor unit *2
-2.5
0.998
0.997
0.990
0.970
0.943
0.917
-5
—
0.995
0.987
0.967
0.940
0.914
-10
—
—
0.982
0.962
0.935
0.910
-15
—
—
—
0.957
0.930
0.905
¢
Indoor unit: 18,000 Btu/h
Cooling
Pipe length
m
2.5
5
10
15
20
25
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
15
—
—
—
0.968
0.961
0.954
10
—
—
0.982
0.976
0.969
0.962
5
—
0.992
0.990
0.984
0.977
0.970
2.5
0.996
0.996
0.994
0.988
0.981
0.974
0
1.000
1.000
0.998
0.992
0.985
0.978
Indoor unit is lower
than outdoor unit *2
-2.5
1.000
1.000
0.998
0.992
0.985
0.978
-5
—
1.000
0.998
0.992
0.985
0.978
-10
—
—
0.998
0.992
0.985
0.978
-15
—
—
—
0.992
0.985
0.978
Heating
Pipe length
m
2.5
5
10
15
20
25
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
15
—
—
—
0.967
0.943
0.917
10
—
—
0.990
0.967
0.943
0.917
5
—
1.000
0.990
0.967
0.943
0.917
2.5
1.000
1.000
0.990
0.967
0.943
0.917
0
1.000
1.000
0.990
0.967
0.943
0.917
Indoor unit is lower
than outdoor unit *2
-2.5
0.998
0.997
0.988
0.965
0.941
0.915
-5
—
0.995
0.985
0.962
0.938
0.912
-10
—
—
0.980
0.958
0.933
0.908
-15
—
—
—
0.953
0.929
0.903
- 428 -
7-1. Model: AOYG36KBTA5
7. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYG36KBTA5
OUTDOOR UNIT
AOYG36KBTA5