Floor type
Model: AGYG09KVCA
Outdoor temperature
Indoor temperature (°CDB)
16.0
18.0
20.0
22.0
24.0
(°CDB)
(°CWB)
TC
TC
TC
TC
TC
-15.0
-16.0
1.97
1.93
1.88
1.83
1.79
-10.0
-11.0
2.46
2.40
2.34
2.28
2.22
-5.0
-7.0
2.92
2.86
2.79
2.72
2.65
0.0
-2.0
3.44
3.36
3.28
3.19
3.11
5.0
3.0
3.78
3.69
3.60
3.51
3.42
7.0
6.0
3.78
3.69
3.60
3.51
3.42
10.0
8.0
3.78
3.69
3.60
3.51
3.42
15.0
10.0
3.78
3.69
3.60
3.51
3.42
20.0
15.0
3.78
3.69
3.60
3.51
3.42
24.0
18.0
3.78
3.69
3.60
3.51
3.42
Model: AGYG12KVCA
Outdoor temperature
Indoor temperature (°CDB)
16.0
18.0
20.0
22.0
24.0
(°CDB)
(°CWB)
TC
TC
TC
TC
TC
-15.0
-16.0
2.63
2.57
2.51
2.44
2.38
-10.0
-11.0
3.28
3.20
3.12
3.04
2.97
-5.0
-7.0
3.90
3.81
3.71
3.62
3.53
0.0
-2.0
4.59
4.48
4.37
4.26
4.15
5.0
3.0
5.04
4.92
4.80
4.68
4.56
7.0
6.0
5.04
4.92
4.80
4.68
4.56
10.0
8.0
5.04
4.92
4.80
4.68
4.56
15.0
10.0
5.04
4.92
4.80
4.68
4.56
20.0
15.0
5.04
4.92
4.80
4.68
4.56
24.0
18.0
5.04
4.92
4.80
4.68
4.56
Model: AGYG14KVCA
Outdoor temperature
Indoor temperature (°CDB)
16.0
18.0
20.0
22.0
24.0
(°CDB)
(°CWB)
TC
TC
TC
TC
TC
-15.0
-16.0
3.07
3.00
2.93
2.85
2.78
-10.0
-11.0
3.82
3.73
3.64
3.55
3.46
-5.0
-7.0
4.55
4.44
4.33
4.22
4.12
0.0
-2.0
5.35
5.22
5.10
4.97
4.84
5.0
3.0
5.88
5.74
5.60
5.46
5.32
7.0
6.0
5.88
5.74
5.60
5.46
5.32
10.0
8.0
5.88
5.74
5.60
5.46
5.32
15.0
10.0
5.88
5.74
5.60
5.46
5.32
20.0
15.0
5.88
5.74
5.60
5.46
5.32
24.0
18.0
5.88
5.74
5.60
5.46
5.32
NOTES:
• TC: Total Capacity (kW)
• Values mentioned in the table are based on the following conditions:
– Pipe length: 5 m, Height difference: 0 m (Outdoor unit—Indoor unit)
- 349 -
6-3. Heating capacity
6. Capacity table
OUTDOOR UNIT
AOYG30KBTA4
OUTDOOR UNIT
AOYG30KBTA4