Indoor unit fan operation status
Mode
Function setting
External output
Output
signal
Command
10
60-10
Output of indoor unit
CN15
Low → High
Fan run
High → Low
Fan stop
0
60-00
CN22
Off → On
Fan run
On → Off
Fan stop
Output signal
Condition
On
The indoor unit fan is operating.
Low → High
Off
The fan is stopped or during cold air prevention.
High → Low
During thermostat off when in dry mode operation.
Fan run
Fan stop
High
Low
CN15
On
Off
CN22
Indoor unit
•
Set point attainment status
NOTE:
This function is valid only when function setting 96 is set to “01” (Primary unit) or “02” (Sec-
ondary unit).
When the room temperature does not reach the set point at a room due to the lower cooling per-
formance caused by external factor such as the outdoor temperature change, signal is output to
tell the attainment status of set point.
Mode
Function setting
External output
Output
signal
Command
12
60-12
Outputof indoor unit
CN15
On → Off
Normal
Off → On
Set point
attainment
Output signal
Condition
Off
Reached the set point. (Tr≤ Tsα + 0.5°C)
On
Unreached the set point. (Tr> Tsα + 2.5°C)
However, even if the set point unreached,the signal will not be output for 7 minutes
after power is turned on.
When performing the server room control, both of the primary unit and secondary unit output the
set point attainment status if any of the unit is outputting alternative operation command.
Tr > Tsα + 2.5°C
Output: On
Output: Off
Tr ≤ Tsα + 0.5°C
When starting operation*
*: When starting operation or resetting, judges the zone to descending direction.
- 188 -
11-5. Floor type
11. External input and output
4-5 UNIT
MULTI-SPLIT TYPE
4-5 UNIT
MULTI-SPLIT TYPE