When function setting is "Operation/Stop" mode 2
Function setting
External input
Input signal
Command
46—03
Terminal
Off → On
Operation
On → Off
Stop (R.C. disabled)
On
Input
Off
Operation
Indoor unit
Stop
(R.C. disabled)
Remote controller
On
On
Off
NOTE:
When "Operation/Stop" mode 2 function is used with forming a remote controller group,
connect the same equipment to each indoor unit within the group.
Control output function
Function setting
External output
Output signal
Command
60—00
CN47
Low → High
Operation
High → Low
Stop
The output is low when the unit is stopped.
Operation
Stop
High
Low
CN47
Indoor unit
Error status
Function setting
External output
Output signal
Command
60—09
CN47
Low → High
Error
High → Low
Normal
The output is ON when an error is generated for the indoor unit.
Error
Normal
High
Low
CN47
Indoor unit