Indoor unit: 9,000 Btu/h
Cooling
Pipe length
m
2.5
5
10
15
20
25
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
15
—
—
—
0.956
0.942
0.928
10
—
—
0.977
0.963
0.950
0.936
5
—
0.992
0.985
0.971
0.957
0.943
2.5
0.996
0.996
0.989
0.975
0.961
0.947
0
1.000
1.000
0.993
0.979
0.965
0.951
Indoor unit is lower
than outdoor unit *2
-2.5
1.000
1.000
0.993
0.979
0.965
0.951
-5
—
1.000
0.993
0.979
0.965
0.951
-10
—
—
0.993
0.979
0.965
0.951
-15
—
—
—
0.979
0.965
0.951
Heating
Pipe length
m
2.5
5
10
15
20
25
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
15
—
—
—
0.977
0.958
0.939
10
—
—
0.993
0.977
0.958
0.939
5
—
1.000
0.993
0.977
0.958
0.939
2.5
1.000
1.000
0.993
0.977
0.958
0.939
0
1.000
1.000
0.993
0.977
0.958
0.939
Indoor unit is lower
than outdoor unit *2
-2.5
0.998
0.997
0.991
0.975
0.956
0.937
-5
—
0.995
0.988
0.972
0.954
0.934
-10
—
—
0.983
0.967
0.949
0.930
-15
—
—
—
0.962
0.944
0.925
¢
Indoor unit: 12,000 Btu/h
Cooling
Pipe length
m
2.5
5
10
15
20
25
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
15
—
—
—
0.937
0.912
0.888
10
—
—
0.970
0.944
0.919
0.896
5
—
0.992
0.978
0.952
0.927
0.903
2.5
0.996
0.996
0.982
0.956
0.930
0.907
0
1.000
1.000
0.986
0.960
0.934
0.910
Indoor unit is lower
than outdoor unit *2
-2.5
1.000
1.000
0.986
0.960
0.934
0.910
-5
—
1.000
0.986
0.960
0.934
0.910
-10
—
—
0.986
0.960
0.934
0.910
-15
—
—
—
0.960
0.934
0.910
Heating
Pipe length
m
2.5
5
10
15
20
25
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
15
—
—
—
0.977
0.958
0.938
10
—
—
0.993
0.977
0.958
0.938
5
—
1.000
0.993
0.977
0.958
0.938
2.5
1.000
1.000
0.993
0.977
0.958
0.938
0
1.000
1.000
0.993
0.977
0.958
0.938
Indoor unit is lower
than outdoor unit *2
-2.5
0.998
0.997
0.991
0.975
0.956
0.936
-5
—
0.995
0.988
0.972
0.953
0.933
-10
—
—
0.983
0.967
0.949
0.929
-15
—
—
—
0.962
0.944
0.924
- 427 -
7-1. Model: AOYG36KBTA5
7. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYG36KBTA5
OUTDOOR UNIT
AOYG36KBTA5