Trouble shooting 4
INDOOR UNIT
INDOOR UNIT Error Method:
Indicate or Display:
Outdoor Unit : No indication
ERROR CODE : E : 04
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
31.7
35°C
39.6
30°C
49.7
62.9
80.3
103
134
176
Resistance Value (k )
25°C
20°C
15°C
10°C
5°C
0°C
Temperature
OK
OK
OK
17.1
20.8
25.6
Resistance Value (k )
50°C
45°C
40°C
Temperature
Indoor Heat Exchanger Temperature
Sensor Error
Indoor Unit Controller PCB Circuit
Heat Exchanger Temperature Thermistor
When Heat Exchanger Temperature Thermistor open or short-circuit is
detected at power ON.
1. Connector connection failure 2.Thermistor failure 3. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Controller PCB.
07-07
THERMISTOR
(PIPE TEMP.)
THERMISTOR
(ROOM TEMP.)
G
R
A
Y
G
R
A
Y
B
LA
C
K
B
LA
C
K
CN5
CN7
CN8
1 2
1 2
1 2
1 2
1 2
Summary of Contents for AB Series A18LATN
Page 2: ...1 SPECIFICATIONS R410A INVERTER Large Ceiling type ...
Page 11: ...2 DIMENSIONS R410A INVERTER Large Ceiling type ...
Page 20: ...3 REFRIGERANT SYSTEM DIAGRAM R410A INVERTER Large Ceiling type ...
Page 21: ...03 01 MODEL AB A18 24LATN AO A18 24LACL 3 REFRIGERANT CIRCUIT ...
Page 22: ...03 02 MODEL AB A36 45LATN AO A36 45LATL ...
Page 23: ...03 03 MODEL ABTA18 24LATN AOTA18 24LACL ...
Page 24: ...03 04 MODEL ABTA36 45LATN AOTA36 45LATL ...
Page 25: ...4 CIRCUIT DIAGRAM R410A INVERTER Large Ceiling type ...
Page 26: ...04 01 MODEL AB A18 24LATN 4 CIRCUIT DIAGRAM ...
Page 27: ...04 02 MODEL AB A36 45LATN ...
Page 28: ...04 03 MODEL ABTA18 24LATN ...
Page 29: ...04 04 MODEL ABTA36 45LATN ...
Page 30: ...04 05 MODEL AO A18 24LACL ...
Page 31: ...04 06 MODEL AO A36 45LATL ...
Page 32: ...04 07 MODEL AOTA18 24LACL ...
Page 33: ...04 08 MODEL AOTA36 45LATL ...
Page 34: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A Large Ceiling type INVERTER ...
Page 59: ...6 REFRIGERANT CAUTION R410A R410A CASSETTE type INVERTER ...
Page 68: ...7 TROUBLE SHOOTING R410A Large Ceiling type INVERTER ...
Page 109: ...8 APPENDING DATA R410A INVERTER Large Ceiling type ...
Page 126: ...9 INSTALLATION MANUAL R410A INVERTER Large Ceiling type ...
Page 131: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan June 2007 Printed in Japan ...