Trouble shooting 18
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 : Check connection of around the Compressor components
OK
OK
OK
OK
Indicate or Display:
ERROR CODE : E : 1A
Check Point 3: Replace Main PCB
Outdoor Unit Main PCB Circuit
Compressor
Compressor rotor location cannot detect
(Permanent Stop)
1. Defective connection of electric components 2. Main PCB failure 3. Compressor failure
If Check Point 1,2 do not improve the symptom, change Main PCB.
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
(Refer to PARTS INFORMATION 2)
For Compressor Terminal, Main PCB
While running the compressor, if the detected rotor location is out of
phase with actual rotor location more than 90 degrees,
the compressor stops.
After the compressor restarts, if the same operation is repeated
within 40sec, the compressor stops again.
If and repeats 5 times, the compressor stops permanently.
07-20
Check Point 1 : Check Noise from Compressor
Turn on Power and check operation noise.
If an abnormal noise show, replace Compressor.
Outdoor Unit (AB*A18L/ 24L) : LED 0.1sec ON/ 2sec OFF
(AB*A36L/ 45L) : LED 13 times blink
Summary of Contents for AB Series A18LATN
Page 2: ...1 SPECIFICATIONS R410A INVERTER Large Ceiling type ...
Page 11: ...2 DIMENSIONS R410A INVERTER Large Ceiling type ...
Page 20: ...3 REFRIGERANT SYSTEM DIAGRAM R410A INVERTER Large Ceiling type ...
Page 21: ...03 01 MODEL AB A18 24LATN AO A18 24LACL 3 REFRIGERANT CIRCUIT ...
Page 22: ...03 02 MODEL AB A36 45LATN AO A36 45LATL ...
Page 23: ...03 03 MODEL ABTA18 24LATN AOTA18 24LACL ...
Page 24: ...03 04 MODEL ABTA36 45LATN AOTA36 45LATL ...
Page 25: ...4 CIRCUIT DIAGRAM R410A INVERTER Large Ceiling type ...
Page 26: ...04 01 MODEL AB A18 24LATN 4 CIRCUIT DIAGRAM ...
Page 27: ...04 02 MODEL AB A36 45LATN ...
Page 28: ...04 03 MODEL ABTA18 24LATN ...
Page 29: ...04 04 MODEL ABTA36 45LATN ...
Page 30: ...04 05 MODEL AO A18 24LACL ...
Page 31: ...04 06 MODEL AO A36 45LATL ...
Page 32: ...04 07 MODEL AOTA18 24LACL ...
Page 33: ...04 08 MODEL AOTA36 45LATL ...
Page 34: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A Large Ceiling type INVERTER ...
Page 59: ...6 REFRIGERANT CAUTION R410A R410A CASSETTE type INVERTER ...
Page 68: ...7 TROUBLE SHOOTING R410A Large Ceiling type INVERTER ...
Page 109: ...8 APPENDING DATA R410A INVERTER Large Ceiling type ...
Page 126: ...9 INSTALLATION MANUAL R410A INVERTER Large Ceiling type ...
Page 131: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan June 2007 Printed in Japan ...