![Fujitsu AB Series A18LATN Service Instruction Download Page 72](http://html.mh-extra.com/html/fujitsu/ab-series-a18latn/ab-series-a18latn_service-instruction_117994072.webp)
Trouble shooting 1
INDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
Check Point 2 : Check Remote Control and Controller PCB
Check Point 1 : Check the connection of terminal
OK
OK
Indicate or Display:
ERROR CODE : E : 00
Outdoor Unit : No indication
Communication Error
(Indoor unit Remote control)
Indoor unit controller PCB circuit
Wired Remote Control
1. Terminal connection abnormal 2. Wired Remote Control failure 3. Controller PCB failure
After turning off the power, check & correct the followings.
Check the connection of terminal between remote control and Indoor unit,
and check if there is a disconnection of the cable.
Upon correcting the removed connector or mis-wiring, reset the power.
Check Voltage at CN14 (terminal 1-3) of Controller PCB.
(Power supply to Remote Control)
>> If it is DC12V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control
>> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
When the indoor unit cannot receive the signal from Wired Remote
more than 10seconds after power ON, or the indoor unit cannot receive
the signal more than 1minute during normal operation.
07-04
7-2 TROUBLE SHOOTING WITH ERROR CODE
Summary of Contents for AB Series A18LATN
Page 2: ...1 SPECIFICATIONS R410A INVERTER Large Ceiling type ...
Page 11: ...2 DIMENSIONS R410A INVERTER Large Ceiling type ...
Page 20: ...3 REFRIGERANT SYSTEM DIAGRAM R410A INVERTER Large Ceiling type ...
Page 21: ...03 01 MODEL AB A18 24LATN AO A18 24LACL 3 REFRIGERANT CIRCUIT ...
Page 22: ...03 02 MODEL AB A36 45LATN AO A36 45LATL ...
Page 23: ...03 03 MODEL ABTA18 24LATN AOTA18 24LACL ...
Page 24: ...03 04 MODEL ABTA36 45LATN AOTA36 45LATL ...
Page 25: ...4 CIRCUIT DIAGRAM R410A INVERTER Large Ceiling type ...
Page 26: ...04 01 MODEL AB A18 24LATN 4 CIRCUIT DIAGRAM ...
Page 27: ...04 02 MODEL AB A36 45LATN ...
Page 28: ...04 03 MODEL ABTA18 24LATN ...
Page 29: ...04 04 MODEL ABTA36 45LATN ...
Page 30: ...04 05 MODEL AO A18 24LACL ...
Page 31: ...04 06 MODEL AO A36 45LATL ...
Page 32: ...04 07 MODEL AOTA18 24LACL ...
Page 33: ...04 08 MODEL AOTA36 45LATL ...
Page 34: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A Large Ceiling type INVERTER ...
Page 59: ...6 REFRIGERANT CAUTION R410A R410A CASSETTE type INVERTER ...
Page 68: ...7 TROUBLE SHOOTING R410A Large Ceiling type INVERTER ...
Page 109: ...8 APPENDING DATA R410A INVERTER Large Ceiling type ...
Page 126: ...9 INSTALLATION MANUAL R410A INVERTER Large Ceiling type ...
Page 131: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan June 2007 Printed in Japan ...