08-13
8-5. FUNCTION SETTING
( Factory setting)
1-1. Setting the Ceiling Height
Follow the instructions in the Local Setup Procedure, which is supplied with the remote control,
in accordance with the installed condition.
After the power is turned on, perform the Function Setting on the remote control.
The settings may be selected between the following two: Function Number or Setting Value.
Settings will not be changed if invalid numbers or setting values are selected.
Setting Description
Function Number
Setting Value
Standard
(2.5m to 3.0m)
High ceiling
(3.0m to 3.5m)
20
00
01
The ceiling height values are fore the 4 way outlet.
Do not change this setting in the 3 way outlet mode.
8-5-1 INDOOR UNIT
Select the setting values in the table below according to the height of the ceiling.
(The unit is factory set to "00".)
( Factory setting)
Setting Description
Function Number
Setting Value
Standard
(2,500 hours)
Long interval
(4,499 hours)
Short interval
(1,250 hours)
High static pressure 3
21
00
01
02
03
1-2. Setting the Filter Sign
The indoor unit has a sign to inform the user that it is time to clean the filter.
Select the time setting for the filter sign display interval in the table below according to
the amount of dust or debris in the room.
(The unit is factory set to "00")
If you do not wish the filter sign to be displayed, select the setting value for "No indication".
1-3. Setting the Cooler Room Temperature Correction
( Factory setting)
Setting Description
Function Number
Setting Value
Standard
Lower control
30
00
01
Depending on the installed environment, the room temperature sensor may require a correction.
The settings may be selected as shown in the table below.
Summary of Contents for AB Series A18LATN
Page 2: ...1 SPECIFICATIONS R410A INVERTER Large Ceiling type ...
Page 11: ...2 DIMENSIONS R410A INVERTER Large Ceiling type ...
Page 20: ...3 REFRIGERANT SYSTEM DIAGRAM R410A INVERTER Large Ceiling type ...
Page 21: ...03 01 MODEL AB A18 24LATN AO A18 24LACL 3 REFRIGERANT CIRCUIT ...
Page 22: ...03 02 MODEL AB A36 45LATN AO A36 45LATL ...
Page 23: ...03 03 MODEL ABTA18 24LATN AOTA18 24LACL ...
Page 24: ...03 04 MODEL ABTA36 45LATN AOTA36 45LATL ...
Page 25: ...4 CIRCUIT DIAGRAM R410A INVERTER Large Ceiling type ...
Page 26: ...04 01 MODEL AB A18 24LATN 4 CIRCUIT DIAGRAM ...
Page 27: ...04 02 MODEL AB A36 45LATN ...
Page 28: ...04 03 MODEL ABTA18 24LATN ...
Page 29: ...04 04 MODEL ABTA36 45LATN ...
Page 30: ...04 05 MODEL AO A18 24LACL ...
Page 31: ...04 06 MODEL AO A36 45LATL ...
Page 32: ...04 07 MODEL AOTA18 24LACL ...
Page 33: ...04 08 MODEL AOTA36 45LATL ...
Page 34: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A Large Ceiling type INVERTER ...
Page 59: ...6 REFRIGERANT CAUTION R410A R410A CASSETTE type INVERTER ...
Page 68: ...7 TROUBLE SHOOTING R410A Large Ceiling type INVERTER ...
Page 109: ...8 APPENDING DATA R410A INVERTER Large Ceiling type ...
Page 126: ...9 INSTALLATION MANUAL R410A INVERTER Large Ceiling type ...
Page 131: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan June 2007 Printed in Japan ...