2. CONDITION OF THE DEFROST OPERATION COMPLETION
Release Condition
Outdoor heat exchanger temperature sensor value is higher than +10
°
C or
Compressor operation time has passed 15 minutes.
1-22. DEFROST OPERATION CONTROL
1. CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts when the outdoor heat exchanger temperature sensor detects
the temperature lower than the values shown in Table 13.
(Table 13 : Condition of starting Defrost Operation)
1st time defrosting after starting operation
Less than 17 min.
17 to 62 min.
62 min. to 4 hours More than 4 hours
Does not operate
- 9
°
C
- 5
°
C
- 3
°
C
Compressor integrating
operation time
Compressor contiguous
operation time
Defrost operation is released when the conditions become as shown in Table 14.
(Table 14 : Defrost Release Condition)
Operation
temperature
Below 10 min.
Above 10 min.
Less than 35 min. 35 min. to 215min 215 min. to 4 hours
Does not operate
- 6
°
C
- 5
°
C
More than 4 hours
- 3
°
C
Compressor integrating
operation time
Compressor contiguous
operation time
Operation
temperature
Below 10 min.
Above 10 min.
Defrosting after 2nd time upon starting operation
Compressor integrating
operation time
Operating condition
Integrating defrost for intermittent operation
Less than 10 min.
If the compressor continuous operation time is less than 10 minutes,
the OFF number of the compressor is counted.
If any defrost operated, the compressor OFF count is cleared.
OFF count of the compressor
40 times
More than 210 min.
Compressor OFF
(at outside air temp.< 2
°
C)
=