03-02
( Factory setting)
Setting Description
Function Number
Setting Value
Standard
Lower control
Slightly warmer control
Warmer control
31
00
01
02
03
1-6. Setting the Heater room temperature correction
Depending on the installed environment, the room temperature sensor may require a correction.
The settings may be changed as shown in the table below.
1-5. Setting the Cooler room temperature correction
( Factory setting)
Setting Description
Function Number
Setting Value
Standard
Slightly lower control
Lower control
Warmar control
30
00
01
02
03
Depending on the installed environment, the room temperature sensor may require a correction.
The settings may be selected as shown in the table below.
When using floor console installation, change the setting value to "01".
(For AB / AR type)
When using floor console installation, change the setting value to "01".
(For AB / AR type)
Select appropriate static pressure according to the installation conditions.
( Factory setting)
1-4. Setting the Static pressure (For AR type)
Setting Description
Function Number
Setting Value
0 Pa
10 Pa
20 Pa
30 Pa
40 Pa
50 Pa
60 Pa
70 Pa
80 Pa
90 Pa
25 Pa [Standard]
26
00
01
02
03
04
05
06
07
08
09
31