Error Contents :
Communication Error
with Standard Remote Controller
Symptom :
Error Code display [ 18 ] Control/Display from Standard Remote is
not available. Other controls are left as they are.
Details :
Condition of occurrence : The communication between Standard Remote and Network Convertor was not normally performed.
Release condition : When the communication between Standard Remote and Network Convertor resumes normal operation.
Cause 2 :
Defective or open connection of cable wire between Network Converter and Connected Remote Controller.
After the following are checked, the power supply is reset.
p
Check connection cable wire between Network Convertor and Connected Remote Controller.
p
Check connection between Control PCB and Terminal.
Cause 3 : Incorrect setting of Network Converter's DIP-SW107[2] (Wired RC Validity setting)
p
Check Network Convertor PCB DIP-SW107[2].
Cause 4 : Incorrect selection of Remote Controller
p
Check connection Remote Controller. (Is it specified with the Installation Manual of Network Convertor?)
OK
Cause 5 :
Incorrect setting of Remote Controller's DIP-SW (Number of connected remote controllers)
p
Check DIP-SW of Remote Controller.
OK
Cause 6 : Defective Remote Controller or Network Convertor.
Replace Remote Controller or Network Convertor.
Cause 1 : External noise
p
After pressing SW104 of Network Convertor PCB for 5 seconds or turning on power.
Does error code display reappear?
It is not a defect of PCB. Remove the surrounding noise source.
Remove the surrounding noise source.
YES
OK
NO
OK
OK
Trouble shooting 75
06-75
Summary of Contents for AB*A12
Page 6: ...1 TEST RUN ...
Page 13: ...2 FUNCTION OF PRINTED CIRCUIT BOARD ...
Page 58: ...3 INVERTER CONTROL ...
Page 62: ...4 OUTDOOR UNIT OPERATION CONTROL ...
Page 74: ...5 INDOOR UNIT OPERATION ...
Page 90: ...6 TROUBLE SHOOTING ...
Page 199: ...7 APPENDING DATA UNIT ...
Page 208: ...07 09 MODELS AU A20 AU A25 AU A30 ...
Page 209: ...07 10 MODELS AU A36 AU A45 AU A54 ...
Page 210: ...07 11 COMPACT DUCT TYPE MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 ...
Page 211: ...07 12 MODEL ARXB25 MODELS ARXB30 ARXB36 ARXB45 LOW STATIC PRESSURE DUCT TYPE ...
Page 212: ...07 13 MODELS ARXA30 ARXA36 ARXA45 MODEL ARXA25 DUCT TYPE ...
Page 213: ...07 14 MODELS ARXC36 ARXC45 ARXC60 HIGH STATIC PRESSURE DUCT TYPE ...
Page 214: ...07 15 MODEL ARXC90 ...
Page 215: ...07 16 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 ...
Page 216: ...07 17 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 ...
Page 217: ...07 18 COMPACT WALL MOUNTED TYPE Comfort model MODELS AS E07 AS E09 AS E12 AS E14 ...
Page 218: ...07 19 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 ...
Page 219: ...07 20 CEILING WALL TYPE MODELS AW A07 AW A09 AW A12 AW A14 AW A18 AW A24 AW A30 ...
Page 220: ...07 21 7 3 2 Outdoor Unit MODELS AJ A72LBTF AJ A90LBTF ...
Page 221: ...07 22 MODEL AJ 126LBTF ...
Page 222: ...07 23 MODELS AJ A72UBTF AJ A90UBTF ...
Page 223: ...07 24 MODEL AJ 126UBTF ...
Page 230: ...8 DISASSEMBLY ILLUSTRATION PARTS LIST ...
Page 232: ...Model AJ 126LBTF 104 111 100 101 107 112 103 105 102 110 106 08 02 ...
Page 233: ...Model AJ 126LBTF 151 150 155 156 154 152 161 158 157 160 159 153 08 03 ...
Page 238: ...Model AJ 126UBTF 100 101 107 105 102 110 106 08 08 104 111 112 ...
Page 243: ...Model AJ A90LBTF 104 111 100 101 107 112 103 105 102 110 106 AJ A72LBTF 08 13 ...
Page 244: ...151 150 155 156 154 152 161 158 157 160 159 153 08 14 Model AJ A90LBTF AJ A72LBTF ...
Page 249: ...Model AJ A90UBTF 100 101 107 105 102 110 106 AJ A72UBTF 08 19 104 111 112 ...
Page 287: ......
Page 289: ......