![Fujitsu AB*A12 Service Manual Download Page 109](http://html.mh-extra.com/html/fujitsu/ab-a12/ab-a12_service-manual_118003109.webp)
Trouble shooting 12
INDOOR UNIT Error Method:
Network Communication Error
Indicate or Display:
Indoor Unit : Operation LED Flash
,
Timer LED 5 Times Blink
Swing LED 1 Time Blink
Outdoor Unit : LED1 Flash, LED6
1Time Blink
ERROR CODE : E : 1F
Detective Actuators:
Indoor unit Controller PCB circuit
Indoor unit Transmission PCB
Detective details:
When the cut-off of network communication is detected (more than 90 seconds
passed since the last receipt of Outdoor unit signal).
Check Point 2 : Check if any outside cause such as voltage drop or noise
Instant voltage drop ------ Check if there is any electric equipment with a large load within the same circuit.
Momentary power failure ----- Check contact failure or leak current in power supply circuit
>>Check Outdoor Unit as well.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which
causes harmonic wave). And check the complete insulation of grounding.
>>If the same symptom does not reappear after resetting the power, possibility of noise is high.
Check Point 1 : Check the connection
After turning off the power, check and correct followings.
p
Is Indoor Transmission PCB loose?
p
Check loose or removed connection of communication line between Indoor
and Outdoor unit.
p
Make sure Terminator (CN22) is located at Controller PCB of Main Unit.
Check Point 3 : Check Transmission PCB and Controller PCB
p
If some of Indoor units have errors, replace Transmission PCB of the Indoor units that have the error.
>>If the symptom does not change, replace Indoor unit Controller PCB.
p
If all the Indoor units have error, check if the Outdoor Unit Transmission PCB has a loose connection (Refer to Trouble Shooting 45).
>>If the symptom does not change, replace Outdoor unit Transmission PCB (Replace Controller PCB if it does not change).
Master Unit Schematic(CN22:TERMINATOR)
OK
OK
Forecast of Cause :
1. Connection failure 2. Outside cause 3. Transmission PCB failure 4. Controller PCB failure
Note : Terminator
Terminator is a resistance that prevents the
reflection of the signal at the end terminal of
the circuit which causes abnormal data
transmission when connecting multiple
devices with 1 piece of cable.
Note : Communication error factor
1)System design (Wiring length or connection
number over)
2)Mis-install (Address setting,Terminal resister,
Disconnection, Ground wire)
3)No power (Include a signal amplifier and turn
on all power supplies.)
06-19
Summary of Contents for AB*A12
Page 6: ...1 TEST RUN ...
Page 13: ...2 FUNCTION OF PRINTED CIRCUIT BOARD ...
Page 58: ...3 INVERTER CONTROL ...
Page 62: ...4 OUTDOOR UNIT OPERATION CONTROL ...
Page 74: ...5 INDOOR UNIT OPERATION ...
Page 90: ...6 TROUBLE SHOOTING ...
Page 199: ...7 APPENDING DATA UNIT ...
Page 208: ...07 09 MODELS AU A20 AU A25 AU A30 ...
Page 209: ...07 10 MODELS AU A36 AU A45 AU A54 ...
Page 210: ...07 11 COMPACT DUCT TYPE MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 ...
Page 211: ...07 12 MODEL ARXB25 MODELS ARXB30 ARXB36 ARXB45 LOW STATIC PRESSURE DUCT TYPE ...
Page 212: ...07 13 MODELS ARXA30 ARXA36 ARXA45 MODEL ARXA25 DUCT TYPE ...
Page 213: ...07 14 MODELS ARXC36 ARXC45 ARXC60 HIGH STATIC PRESSURE DUCT TYPE ...
Page 214: ...07 15 MODEL ARXC90 ...
Page 215: ...07 16 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 ...
Page 216: ...07 17 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 ...
Page 217: ...07 18 COMPACT WALL MOUNTED TYPE Comfort model MODELS AS E07 AS E09 AS E12 AS E14 ...
Page 218: ...07 19 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 ...
Page 219: ...07 20 CEILING WALL TYPE MODELS AW A07 AW A09 AW A12 AW A14 AW A18 AW A24 AW A30 ...
Page 220: ...07 21 7 3 2 Outdoor Unit MODELS AJ A72LBTF AJ A90LBTF ...
Page 221: ...07 22 MODEL AJ 126LBTF ...
Page 222: ...07 23 MODELS AJ A72UBTF AJ A90UBTF ...
Page 223: ...07 24 MODEL AJ 126UBTF ...
Page 230: ...8 DISASSEMBLY ILLUSTRATION PARTS LIST ...
Page 232: ...Model AJ 126LBTF 104 111 100 101 107 112 103 105 102 110 106 08 02 ...
Page 233: ...Model AJ 126LBTF 151 150 155 156 154 152 161 158 157 160 159 153 08 03 ...
Page 238: ...Model AJ 126UBTF 100 101 107 105 102 110 106 08 08 104 111 112 ...
Page 243: ...Model AJ A90LBTF 104 111 100 101 107 112 103 105 102 110 106 AJ A72LBTF 08 13 ...
Page 244: ...151 150 155 156 154 152 161 158 157 160 159 153 08 14 Model AJ A90LBTF AJ A72LBTF ...
Page 249: ...Model AJ A90UBTF 100 101 107 105 102 110 106 AJ A72UBTF 08 19 104 111 112 ...
Page 287: ......
Page 289: ......