Description
Operation
During a test operation, Operation LED and Timer LED
repeat flashing at the same time.
If a power is cut off during the operation by such as power
failure, Operation LED and Timer LED flashes alternately.
Operation LED is flashing
During the anti-freezing, Operation LED lights up (Low
Light).
Operation LED is lighting (Low light)
Operation LED is lighting
Timer LED is 3 sec ON, 1sec OFF
During the defrost and the oil recovery operation, only
Operation LED flashes.
Following conditions of Indoor unit are not defects.
During low pressure protection stop (when lower than
0.1MPa of low pressure is detected), LED1 lights up
continuously and LED6 repeats 3 times flashing.
During discharge temperature protection stop (when higher
than 120°C of discharge temperature is detected), LED1
lights up continuously and LED6 repeats 1 time flashing.
LED1 is lighting, and LED6 is flashing
During high pressure protection stop (when higher than
4.1MPa of high pressure is detected), LED1 lights up
continuously and LED6 repeats 2 times flashing.
During test operation, LED1 lights up continuously and
LED5 repeats 3 times flashing.
During oil balance operation, LED1 lights up continuously
and LED5 repeats 4 times flashing.
Description
Operation
During pressure balance, LED1 and LED4 light up continuously.
LED1 and LED4 are lighting
While stopping (idling), only LED1 lights up continuously.
Only LED1 is lighting
When the pump down is completed, LED1 lights up
continuously and LED2,3,4,5,6 repeat 2 times flashing.
LED1 is lighting, and all other LEDs are
flashing
During defrost operation, LED1 lights up continuously and
LED5 repeats 2 times flashing.
During oil recovery, LED1 lights up continuously and LED5
repeats 1 time flashing.
LED1 is lighting, and LED5 is flashing
Following conditions of Outdoor unit are not defects.
06-03
At the heat pump type, indoor unit operation will be different
from outdoor unit operation mode.
The timer lamp indicate as above mentioned.
6-1-3 Operation Not Trouble
Summary of Contents for AB*A12
Page 6: ...1 TEST RUN ...
Page 13: ...2 FUNCTION OF PRINTED CIRCUIT BOARD ...
Page 58: ...3 INVERTER CONTROL ...
Page 62: ...4 OUTDOOR UNIT OPERATION CONTROL ...
Page 74: ...5 INDOOR UNIT OPERATION ...
Page 90: ...6 TROUBLE SHOOTING ...
Page 199: ...7 APPENDING DATA UNIT ...
Page 208: ...07 09 MODELS AU A20 AU A25 AU A30 ...
Page 209: ...07 10 MODELS AU A36 AU A45 AU A54 ...
Page 210: ...07 11 COMPACT DUCT TYPE MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 ...
Page 211: ...07 12 MODEL ARXB25 MODELS ARXB30 ARXB36 ARXB45 LOW STATIC PRESSURE DUCT TYPE ...
Page 212: ...07 13 MODELS ARXA30 ARXA36 ARXA45 MODEL ARXA25 DUCT TYPE ...
Page 213: ...07 14 MODELS ARXC36 ARXC45 ARXC60 HIGH STATIC PRESSURE DUCT TYPE ...
Page 214: ...07 15 MODEL ARXC90 ...
Page 215: ...07 16 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 ...
Page 216: ...07 17 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 ...
Page 217: ...07 18 COMPACT WALL MOUNTED TYPE Comfort model MODELS AS E07 AS E09 AS E12 AS E14 ...
Page 218: ...07 19 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 ...
Page 219: ...07 20 CEILING WALL TYPE MODELS AW A07 AW A09 AW A12 AW A14 AW A18 AW A24 AW A30 ...
Page 220: ...07 21 7 3 2 Outdoor Unit MODELS AJ A72LBTF AJ A90LBTF ...
Page 221: ...07 22 MODEL AJ 126LBTF ...
Page 222: ...07 23 MODELS AJ A72UBTF AJ A90UBTF ...
Page 223: ...07 24 MODEL AJ 126UBTF ...
Page 230: ...8 DISASSEMBLY ILLUSTRATION PARTS LIST ...
Page 232: ...Model AJ 126LBTF 104 111 100 101 107 112 103 105 102 110 106 08 02 ...
Page 233: ...Model AJ 126LBTF 151 150 155 156 154 152 161 158 157 160 159 153 08 03 ...
Page 238: ...Model AJ 126UBTF 100 101 107 105 102 110 106 08 08 104 111 112 ...
Page 243: ...Model AJ A90LBTF 104 111 100 101 107 112 103 105 102 110 106 AJ A72LBTF 08 13 ...
Page 244: ...151 150 155 156 154 152 161 158 157 160 159 153 08 14 Model AJ A90LBTF AJ A72LBTF ...
Page 249: ...Model AJ A90UBTF 100 101 107 105 102 110 106 AJ A72UBTF 08 19 104 111 112 ...
Page 287: ......
Page 289: ......