04-06
When turning on DipSW2-2(Snow falling protection fan mode) and the outdoor unit is stopping
and Tout is below 5 , fan control enters Snow falling protection fan mode.
When the outdoor unit starts the operation or Tout is above 7 ,
fan control exits Snow falling protection fan mode.
Snow falling protection fan mode : Outdoor unit fan operates on
"Hi" mode for 1 minute in every 30 minutes.
4-3-3 Snow falling protection fan mode
EEV 1
EEV 2
Turn on outdoor unit power
Turn on outdoor unit power
EEV is controlled so that the system reaches closer to the target discharge temperature that is calculated from
high and low pressure.
< Cooling mode >
< Heating mode >
500 pulses basically.
24 hours have passed since
the last initialization,and the
outdoor unit has stopped.
Initialization conditions
Control range
operation
stop
refrigerant
discharge
refrigerant
storage
0 - 500 pulses
0 - 500 pulses
0 pulses
0 pulses
Controlled
0 pulses
500 pulses
400 pulses
4-4 EXPANSION VALVE CONTROL
4-5 SPECIAL OPERATION
4-5-1 Oil recovery operation
(1) Purpose of the operation
The amount of refrigerant lubricant oil which has been transported to the indoor units
and the connection pipe with the refrigerant will become large as the operation time of compressor increases.
It is necessary to recover the oil back into the outdoor unit for a certain time interval
in order to prevent compressors from damaging due to lack of lubrication oil.
During the oil recovery operation, appears on the display of wired and central remote controller,
and appears on the simple remote controller.
The operation indicators (LED) of the indoor units flash slowly.
Operating compressor : 2 compressors of each slave type outdoor unit
DC inverter compressor of master type outdoor unit (at 70Hz) and 1 constant
speed compressor.
EEV Opening (Indoor/Outdoor unit): Controlled pulse (as normal operation mode).
FAN speed (Indoor/Outdoor unit) : Controlled fan speed (as normal operation mode).
Oil recovery operation time : When suction sensor temperarure(Thermistor11) of master unit
detects fall in the certain temperature, oil recovery operation is terminated.
Oil recovery operation time is a maximum of 6 minutes.
(2) Starting conditions
(3) Operation
(4) Others
Starting conditions of oil recovery operation are as follows.
Indoor EEV is gradually opened. (Oil is recovered together with refrigerant.)
Accumulated time of oil recovery operation 3(Cooling) / 8(Heating) hours
Oil recovery from the gas main pipe (Only cooling mode)
If the overheating condition is continued over 30 minutes, where the difference between compressor suction
sensor temperature and low pressure sensor temperature (Suction SH) is higher than 10degC (Normal control
if Suction SH becomes small afterward),
1
1
2
2
Summary of Contents for AB*A12
Page 6: ...1 TEST RUN ...
Page 13: ...2 FUNCTION OF PRINTED CIRCUIT BOARD ...
Page 58: ...3 INVERTER CONTROL ...
Page 62: ...4 OUTDOOR UNIT OPERATION CONTROL ...
Page 74: ...5 INDOOR UNIT OPERATION ...
Page 90: ...6 TROUBLE SHOOTING ...
Page 199: ...7 APPENDING DATA UNIT ...
Page 208: ...07 09 MODELS AU A20 AU A25 AU A30 ...
Page 209: ...07 10 MODELS AU A36 AU A45 AU A54 ...
Page 210: ...07 11 COMPACT DUCT TYPE MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 ...
Page 211: ...07 12 MODEL ARXB25 MODELS ARXB30 ARXB36 ARXB45 LOW STATIC PRESSURE DUCT TYPE ...
Page 212: ...07 13 MODELS ARXA30 ARXA36 ARXA45 MODEL ARXA25 DUCT TYPE ...
Page 213: ...07 14 MODELS ARXC36 ARXC45 ARXC60 HIGH STATIC PRESSURE DUCT TYPE ...
Page 214: ...07 15 MODEL ARXC90 ...
Page 215: ...07 16 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 ...
Page 216: ...07 17 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 ...
Page 217: ...07 18 COMPACT WALL MOUNTED TYPE Comfort model MODELS AS E07 AS E09 AS E12 AS E14 ...
Page 218: ...07 19 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 ...
Page 219: ...07 20 CEILING WALL TYPE MODELS AW A07 AW A09 AW A12 AW A14 AW A18 AW A24 AW A30 ...
Page 220: ...07 21 7 3 2 Outdoor Unit MODELS AJ A72LBTF AJ A90LBTF ...
Page 221: ...07 22 MODEL AJ 126LBTF ...
Page 222: ...07 23 MODELS AJ A72UBTF AJ A90UBTF ...
Page 223: ...07 24 MODEL AJ 126UBTF ...
Page 230: ...8 DISASSEMBLY ILLUSTRATION PARTS LIST ...
Page 232: ...Model AJ 126LBTF 104 111 100 101 107 112 103 105 102 110 106 08 02 ...
Page 233: ...Model AJ 126LBTF 151 150 155 156 154 152 161 158 157 160 159 153 08 03 ...
Page 238: ...Model AJ 126UBTF 100 101 107 105 102 110 106 08 08 104 111 112 ...
Page 243: ...Model AJ A90LBTF 104 111 100 101 107 112 103 105 102 110 106 AJ A72LBTF 08 13 ...
Page 244: ...151 150 155 156 154 152 161 158 157 160 159 153 08 14 Model AJ A90LBTF AJ A72LBTF ...
Page 249: ...Model AJ A90UBTF 100 101 107 105 102 110 106 AJ A72UBTF 08 19 104 111 112 ...
Page 287: ......
Page 289: ......