Trouble shooting 14
OUTDOOR UNIT Error Method:
Compressor 2 Abnormal
(Constant Speed)
Indicate or Display:
Outdoor Unit : LED1 Flash, LED2
2 Time Blink
Indoor Unit : Operation LED Flash, Timer LED 3 Time Blinks,
ERROR CODE : E : 32
Detective Actuators:
Outdoor Unit Controller PCB circuit
Discharge Thermistor
Detective details:
Compressor 2 detects 5 times of cases that discharge temperature
does not rise to more than 5 °C within 10 minutes after start.
Check Point 2 : Check Magnet Relay
Check Point 3 : Check Compressor
If the symptom does not change with Check Point 1 and 2, a failure of
Constant speed Compressor can be suspected. (PARTS INFORMATION 1,2)
OK
OK
Check Point 1 : Check Discharge Thermistor
p
Check if other type of thermistor is wrongly installed.
p
Check if the thermistor is removed from the holder.
p
Check if the cable of the thermistor is pinched.
>>Check characteristics of Thermistor (Refer to Trouble shooting 22, 23, 24)
If defective, replace the thermistor.
Forecast of Cause :
1. Discharge Thermistor mis-installed 2. Magnet Relay failure 3. Constant speed Compressor failure
p
Check if the connector between Magnet Relay and PCB is loose.
p
Check if the connector between Magnet Relay and PCB is reversed.
p
Check the operation by pressing the Magnet Relay.
>>If it does not operate, check if it is corrected by replacing with other magnet
relay, and if it operates, replace the Magnet Relay.
06-23
Swing LED 3 Time Blinks
When Discharge temp protection operates 3 times within 40 minutes,
the compressor stops permanently.
[ CHECK 1 ]
Summary of Contents for AB*A12
Page 6: ...1 TEST RUN ...
Page 13: ...2 FUNCTION OF PRINTED CIRCUIT BOARD ...
Page 58: ...3 INVERTER CONTROL ...
Page 62: ...4 OUTDOOR UNIT OPERATION CONTROL ...
Page 74: ...5 INDOOR UNIT OPERATION ...
Page 90: ...6 TROUBLE SHOOTING ...
Page 199: ...7 APPENDING DATA UNIT ...
Page 208: ...07 09 MODELS AU A20 AU A25 AU A30 ...
Page 209: ...07 10 MODELS AU A36 AU A45 AU A54 ...
Page 210: ...07 11 COMPACT DUCT TYPE MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 ...
Page 211: ...07 12 MODEL ARXB25 MODELS ARXB30 ARXB36 ARXB45 LOW STATIC PRESSURE DUCT TYPE ...
Page 212: ...07 13 MODELS ARXA30 ARXA36 ARXA45 MODEL ARXA25 DUCT TYPE ...
Page 213: ...07 14 MODELS ARXC36 ARXC45 ARXC60 HIGH STATIC PRESSURE DUCT TYPE ...
Page 214: ...07 15 MODEL ARXC90 ...
Page 215: ...07 16 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 ...
Page 216: ...07 17 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 ...
Page 217: ...07 18 COMPACT WALL MOUNTED TYPE Comfort model MODELS AS E07 AS E09 AS E12 AS E14 ...
Page 218: ...07 19 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 ...
Page 219: ...07 20 CEILING WALL TYPE MODELS AW A07 AW A09 AW A12 AW A14 AW A18 AW A24 AW A30 ...
Page 220: ...07 21 7 3 2 Outdoor Unit MODELS AJ A72LBTF AJ A90LBTF ...
Page 221: ...07 22 MODEL AJ 126LBTF ...
Page 222: ...07 23 MODELS AJ A72UBTF AJ A90UBTF ...
Page 223: ...07 24 MODEL AJ 126UBTF ...
Page 230: ...8 DISASSEMBLY ILLUSTRATION PARTS LIST ...
Page 232: ...Model AJ 126LBTF 104 111 100 101 107 112 103 105 102 110 106 08 02 ...
Page 233: ...Model AJ 126LBTF 151 150 155 156 154 152 161 158 157 160 159 153 08 03 ...
Page 238: ...Model AJ 126UBTF 100 101 107 105 102 110 106 08 08 104 111 112 ...
Page 243: ...Model AJ A90LBTF 104 111 100 101 107 112 103 105 102 110 106 AJ A72LBTF 08 13 ...
Page 244: ...151 150 155 156 154 152 161 158 157 160 159 153 08 14 Model AJ A90LBTF AJ A72LBTF ...
Page 249: ...Model AJ A90UBTF 100 101 107 105 102 110 106 AJ A72UBTF 08 19 104 111 112 ...
Page 287: ......
Page 289: ......