10.2 Wiring diagram 

(1) 3-wire control circuit 

(2) 2-wire control circuit 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
In 2-wire control circuits, be careful of the following points when using thermal overload relay with setting reset 
button to auto reset mode. If over-current flows, which is not large enough to blow the fuse or to operate the circuit 
breaker, the magnetic contactor repeats make/break operations. It does this because the thermal overload relay 
repeats the resets and the trips automatically. This repeated make/break operations would damage the magnetic 
contactor and the thermal overload relay. Eventually, contact welding short-circuit (phase to phase) or grounding 
occur, and the fuse blow or circuit breaker operate. In this case, check the magnetic contactor and the thermal 
overload relay. Replace them if they have been damaged. 
 

Master SW 

by customer

 

Summary of Contents for TK13

Page 1: ...manual and make sure that it is delivered without fail over to the hands of the person who takes the final responsibility for operation and maintenance Type TK13 1 2 3 TK25 3 TK26 1 2 3 TK26E 3 1 L Lo...

Page 2: ...arning and Caution Indicates a potentially hazardous situation which if not avoided may result in death or serious injury Indicates a potentially hazardous situation which if not avoided may result in...

Page 3: ...3 3 Interpretation of Manufacturing Lot Number 4 4 Unpacking 5 5 Precautions in Handling Unpacking and Storage 5 6 Mounting 5 7 Wiring 6 8 Usage Instructions 7 9 Maintenance and Inspection 9 9 1 Insp...

Page 4: ...of Manufacturing Lot Number Example 3 2 01 a b c a Last digit of the Christian year 3 Year 2013 b Manufactured month 2 February 1 January 2 February 9 September 0 October X November Y December c Manu...

Page 5: ...ints with regard to the space for mounting Figure 6 2 Provide a space of at least the value shown in the Figure below The dimension C is a value specified under the short circuit breaking capacity tes...

Page 6: ...pcs x 16 to 14 2 pcs x 14 to 12 1 pc x 18 to 12 2 pcs x 18 to 12 1 pc x 18 to 14 2 pcs x 18 to 16 2 pcs x 16 to 14 Sleeve dimension mm 10 11 10 Crimp terminal connection Twisted wire flexible twisted...

Page 7: ...uit d Tighten the terminal screws of the magnetic contactor to the specified torque Refer to the instruction manual for magnetic contactors Remove the thermal overload relay according to the following...

Page 8: ...0 lower than the dial set value TK26QH 12 18A Set to a value 10 lower than the dial set value 4 Operating indicator Figure 8 4 When the thermal overload relay operates the white trip indicator in the...

Page 9: ...a reactor and power must be supplied to each one of those phases 9 Maintenance and Inspection 9 1 Inspection before Operation 1 Check if there are any loose screws 2 Check if there are any wire scraps...

Page 10: ...aiting A SCCR kA Circuit Breaker Raiting A Fuse Raiti ng A 0 1 0 15 0 13 0 2 0 18 0 27 0 24 0 36 0 34 0 52 0 48 0 72 0 64 0 96 0 8 1 2 0 95 1 45 1 1 1 65 1 4 2 1 1 7 2 6 2 2 3 4 2 8 4 2 4 6 5 7 5 6 9...

Page 11: ...aker the magnetic contactor repeats make break operations It does this because the thermal overload relay repeats the resets and the trips automatically This repeated make break operations would damag...