Table 13: Examples of EtherNet/IP-Style Bulk Access via File N60
Offset/Element
Start Target Function
Code of Configuration
Array
Max Number of
Accessible Elements
0
1
st
32
:
: :
15
16
th
16
:
: :
31
32
nd
1
The application PLC program uses a MSG instruction that is configured with a “Data Table Address”
from which to start the access and a “Size in Elements” which determines the number of items to access
(read or write). The “Data Table Address” is constructed by selecting a “File/Section Number” and an
“Offset/Element” according to Equation 7. For example, a “File/Section Number” of N27 and
“Offset/Element” of 99 = N27:99, which corresponds to register 1799 (the inverter’s operation command
register, function code S06).