1-3
In this manual, inverter types are denoted as "FRN_ _ _LM2A- _
o
." The boxes
o
replace alphabetic
letters depending on the shipping destination.
If you suspect the product is not working properly or if you have any questions about your product, contact your
Fuji Electric representative.
PG interface card is available to the following ROM versions.
&
For detailed on how to check the ROM version, refer to the FRENIC-Lift LM2A series Reference Manual.
Table 1.1 PG interface card, and ROM Versions
PG interface card
ROM Versions
OPC-PR/PS/PSH
0300 or later
OPC-PG3/PMPG
0600 or later
1.2
Precautions for Using Inverters
When handling inverters, be sure to observe the wiring precautions given below.
(1) The maximum wiring distance between an inverter and a motor
The maximum wiring is 20m.
When using wire longer than the specification, that may not be able to control a motor.
If longer secondary wiring is required, consult your Fuji Electric representative.
Motor
Inverter
Power
input
Max. 20 m