10.5 Conformity with the EMC Directive in the EU
10.5.1 General
The CE Marking on inverters does not ensure that the entire equipment including CE-marked products is
compliant with the EMC Directive. Therefore, it is the responsibility of the equipment manufacturer to ensure
that the equipment including the product (inverter) or connected with it actually complies with the standard and
to put a CE Marking as the equipment.
In general, the user’s equipment comprises a variety of products supplied from a number of manufacturers in
addition to Fuji inverters. Therefore, the manufacturer of the final equipment needs to take responsibility for
conformity.
In addition, to satisfy the requirements noted above, it is necessary to use a Fuji inverter in connection with an
EMC-compliant filter (option) and install it in accordance with the instructions contained in this instruction
manual. Install the Fuji inverter in a metal enclosure.
To use Fuji EMC-filter built-in inverters, refer to the FRENIC-Eco Instruction Manual Supplement for
EMC-Filter Built-in Type, Chapter 10, "CONFORMITY WITH STANDARDS."
10.5.2 EMC-compliant filter (Option)
There are two installation styles of an optional EMC-compliant filter--Footmount and split styles. As listed on the
next page, the footmount style applies to inverters with 3-phase 460 V, 1 to 30HP for 460V, and the split style, to
inverters with 3-phase 208 V 30 to125HP, 3-phase 460 V 40 to 350HP.
For how to install the EMC-compliant filter, see Section 10.5.3 “Recommended installation of EMC-compliant
filter.”
The use of an EMC-compliant filter increases leakage current as shown on the next page.
Summary of Contents for FRENIC-ECO
Page 111: ...5 3 F codes Fundamental Functions The shaded function codes are applicable to the quick setup...
Page 114: ...5 6 F code continued...
Page 115: ...5 7 E codes Extension Terminal Functions...
Page 116: ...5 8 E code continued...
Page 119: ...5 11 E code continued...
Page 121: ...5 13 P codes Motor Parameters The shaded function codes are applicable to the quick setup...
Page 122: ...5 14 H codes High Performance Functions...
Page 123: ...5 15 H code continued...
Page 126: ...5 18 J code continued...
Page 127: ...5 19 J code continued...
Page 128: ...5 20 y codes Link Functions...
Page 129: ...5 21 y code continued...
Page 141: ...5 33 Example of Operating Characteristics...
Page 217: ...8 6 8 3 Common Specifications...
Page 218: ...8 7...
Page 223: ...8 12 8 5 External Dimensions 8 5 1 Standard models Unit inch mm 10 2 260...
Page 227: ...8 16 8 5 3 Multi function Keypad Unit inch mm...
Page 246: ...Fuji Electric FA Components Systems Co Ltd Fuji Electric Corp of America 2007 11 K07 K07 10CM...