• When the inverter is driven by an external analog frequency command sources (terminals [12],
[C1], and [V2]):
The "Switch normal/inverse operation" command (IVS) can apply only to the analog frequency
command sources (terminals [12], [C1] and [V2]) in frequency command 1 (F01) and does not
affect frequency command 2 (C30) or UP/DOWN control.
As listed below, the combination of the "Selection of normal/inverse operation for frequency
command 1" (C53) and "Switch normal/inverse operation" (IVS) determines the final operation.
Combination of C53 and (IVS)
Data for C53
(IVS)
Final operation
OFF
Normal
0: Normal operation
ON
Inverse
OFF
Inverse
1: Inverse operation
ON
Normal
Interlock -- (IL)
(Function code data = 22)
In a configuration where a magnetic contactor (MC) is installed in the power output (secondary)
circuit of the inverter, the momentary power failure detection feature provided inside the inverter
may not be able to accurately detect a momentary power failure by itself. Using a digital signal
input with the interlock command (IL) assures the accurate detection
(IL) Meaning
OFF
No momentary power failure has occurred.
ON
A momentary power failure has occurred.
(Restart after a momentary power failure enabled)
For details of operation after a recovery from momentary power failure, refer to the
description of function code F14.
Enable communications link via RS-485 or field bus (option) -- (LE)
(Function code data = 24)
Turning this terminal command ON assigns priorities to frequency commands or run commands
received via the RS-485 communications link (H30) or the field bus option (y98).
No (LE) assignment is functionally equivalent to the (LE) being ON.
For details of switching,
refer to H30 (Communications link function) and y98 (Bus link
function.
Summary of Contents for FRENIC-ECO
Page 111: ...5 3 F codes Fundamental Functions The shaded function codes are applicable to the quick setup...
Page 114: ...5 6 F code continued...
Page 115: ...5 7 E codes Extension Terminal Functions...
Page 116: ...5 8 E code continued...
Page 119: ...5 11 E code continued...
Page 121: ...5 13 P codes Motor Parameters The shaded function codes are applicable to the quick setup...
Page 122: ...5 14 H codes High Performance Functions...
Page 123: ...5 15 H code continued...
Page 126: ...5 18 J code continued...
Page 127: ...5 19 J code continued...
Page 128: ...5 20 y codes Link Functions...
Page 129: ...5 21 y code continued...
Page 141: ...5 33 Example of Operating Characteristics...
Page 217: ...8 6 8 3 Common Specifications...
Page 218: ...8 7...
Page 223: ...8 12 8 5 External Dimensions 8 5 1 Standard models Unit inch mm 10 2 260...
Page 227: ...8 16 8 5 3 Multi function Keypad Unit inch mm...
Page 246: ...Fuji Electric FA Components Systems Co Ltd Fuji Electric Corp of America 2007 11 K07 K07 10CM...