8-11
(Note 5) Normally no need to be connected. Use these terminals when the inverter is equipped with a high power factor
PWM converter with a regenerative facility.
(Note 6) You can select the frequency command source either electronically by supplying a DC voltage signal (within
the range of 0 to 10 V, 0 to 5 V, or 1 to 5 V) between terminals [12] and [11], or manually by connecting a
frequency command potentiometer to terminals [13], [12], and [11].
(Note 7) For the wiring of the control circuit, use shielded or twisted wires. When using shielded wires, connect the
shields to earth. To prevent malfunction due to noise, keep the control circuit wires as far away as possible
from the main circuit wires (recommended distance: 10 cm or longer), and never put them in the same wire
duct. Where a control circuit wire needs to cross a main circuit wire, route them so that they meet at right
angles.
Summary of Contents for FRENIC-ECO
Page 111: ...5 3 F codes Fundamental Functions The shaded function codes are applicable to the quick setup...
Page 114: ...5 6 F code continued...
Page 115: ...5 7 E codes Extension Terminal Functions...
Page 116: ...5 8 E code continued...
Page 119: ...5 11 E code continued...
Page 121: ...5 13 P codes Motor Parameters The shaded function codes are applicable to the quick setup...
Page 122: ...5 14 H codes High Performance Functions...
Page 123: ...5 15 H code continued...
Page 126: ...5 18 J code continued...
Page 127: ...5 19 J code continued...
Page 128: ...5 20 y codes Link Functions...
Page 129: ...5 21 y code continued...
Page 141: ...5 33 Example of Operating Characteristics...
Page 217: ...8 6 8 3 Common Specifications...
Page 218: ...8 7...
Page 223: ...8 12 8 5 External Dimensions 8 5 1 Standard models Unit inch mm 10 2 260...
Page 227: ...8 16 8 5 3 Multi function Keypad Unit inch mm...
Page 246: ...Fuji Electric FA Components Systems Co Ltd Fuji Electric Corp of America 2007 11 K07 K07 10CM...