5-26
F04
F05
H50
H51
Base Frequency
Rated Voltage at Base Frequency
Non-linear V/f Pattern (Frequency)
Non-linear V/f Pattern (Voltage)
These function codes specify the base frequency and the voltage at the base frequency
essentially required for running the motor properly. If combined with the related function codes
H50 and H51, these function codes may profile the non-linear V/f pattern by specifying increase
or decrease in voltage at any point on the V/f pattern.
The following description includes setups required for the non-linear V/f pattern.
At high frequencies, the motor impedance may increase, resulting in an insufficient output voltage
and a decrease in output torque. This feature is used to increase the voltage at high frequencies
to prevent this problem from happening. Note, however, that you cannot increase the output
voltage beyond the voltage of the inverter’s input power.
Base Frequency (F04)
Set the rated frequency printed on the nameplate labeled on the motor.
Rated Voltage at Base Frequency (F05)
Set 0 or the rated voltage printed on the nameplate labeled on the motor.
- If 0 is set, the rated voltage at base frequency is determined by the power source of the inverter.
The output voltage will vary in line with any variance in input voltage.
- If the data is set to anything other than 0, the inverter automatically keeps the output voltage
constant in line with the setting. When any of the automatic torque boost settings, automatic
energy saving or slip compensation is active, the voltage settings should be equal to the rated
voltage of the motor.
Non-linear V/f Pattern for Frequency (H50)
Set the frequency component at an arbitrary point of the non-linear V/f pattern.
(Setting 0.0 to H50 disables the non-linear V/f pattern operation.)
Non-linear V/f Pattern for Voltage (H51)
Sets the voltage component at an arbitrary point of the non-linear V/f pattern.
If the rated voltage at base frequency (F05) is set to 0, settings of function codes H50
and H51 will be ignored.
If the auto torque boost (F37) is enabled, H50 and H51 will be ignored.
Factory settings:
For models of 25HP for 208V, 30HP for 460V or below the non-linear V/f is disabled
(H50 = 0, H51 = 0.)
For models of 30HP for 208V, 40HP for 460V or above it is enabled, that is, (H50 = 5
Hz, H51 = 20 V), for the 208 V, (H50 = 5 Hz, H51 = 40 V) for 460 V.
Rated input voltage
Function
code
Name
Rated
capacity
(HP)
208 V
460 V
F04
Base Frequency
7.5 to 100
50.0 Hz
50.0 Hz
F05 Rated
Voltage
at Base Frequency
7.5 to 100
208 V
460 V
40 or below
0 Hz
0 Hz
H50
Non-linear V/f Pattern
(Frequency)
50 or above
5.0 Hz
5.0 Hz
40 or below
0 Hz
0 Hz
H51
Non-linear V/f Pattern
(Voltage)
50 or above
20 V
40 V
Summary of Contents for FRENIC-ECO
Page 111: ...5 3 F codes Fundamental Functions The shaded function codes are applicable to the quick setup...
Page 114: ...5 6 F code continued...
Page 115: ...5 7 E codes Extension Terminal Functions...
Page 116: ...5 8 E code continued...
Page 119: ...5 11 E code continued...
Page 121: ...5 13 P codes Motor Parameters The shaded function codes are applicable to the quick setup...
Page 122: ...5 14 H codes High Performance Functions...
Page 123: ...5 15 H code continued...
Page 126: ...5 18 J code continued...
Page 127: ...5 19 J code continued...
Page 128: ...5 20 y codes Link Functions...
Page 129: ...5 21 y code continued...
Page 141: ...5 33 Example of Operating Characteristics...
Page 217: ...8 6 8 3 Common Specifications...
Page 218: ...8 7...
Page 223: ...8 12 8 5 External Dimensions 8 5 1 Standard models Unit inch mm 10 2 260...
Page 227: ...8 16 8 5 3 Multi function Keypad Unit inch mm...
Page 246: ...Fuji Electric FA Components Systems Co Ltd Fuji Electric Corp of America 2007 11 K07 K07 10CM...