(a) A.V.R. TROUBLE IDENTIFICATION by APPEARANCE
If an A.V.R. electronic part is burnt dark, or the surface epoxy resin melted, it often indicates
A.V.R. trouble.
(b) IDENTIFYING A.V.R. TROUBLE by CHECKING INTER-LEAD RESISTANCE
Check the inter-lead resistance of the A.V.R. with a tester, referring to the following table.
If the tester readings very greatly from the values specified in the table on next page, the A.V.R.
is faulty.
NOTE: Take tester inaccuracy into account in reading the tester.
*Checking table for analogue circuit tester
(c) IDENTIFYING A.V.R. TROUBLE by MOUNTING and OPERATING in THE GENERATOR
SCR or transistor damage cannot be detected by simply looking at the A.V.R. or checking the
lead resistance. Check it by mounting the suspected faulty A.V.R. in a normal generator, or
mount a normal A.V.R. in a generator which fails to generate voltage.
Summary of Contents for ROBIN RGX6500
Page 1: ...1 RGX6500 RGX7500 FUJI HEAVY INDUSTRIES LTD...
Page 2: ...2...
Page 3: ...3 1 SPECIFICATIONS...
Page 4: ...4 2 PERFORMANCE CURVES RGX6500 60Hz 240V RGX7500 60Hz 240V...
Page 5: ...5 3 GENERAL DESCRIPTION Canister...
Page 6: ...6 CONTROL PANEL 50Hz 220V 240V 60Hz 220V 240V 60Hz 110 220V...
Page 7: ...7 SERIAL NUMBER CONSTRUCTION RGX6500 RGX7500 Isolator Slip Ring Through Bolt...
Page 11: ...11 5 MEASURING PROCEDURES...
Page 12: ...12...
Page 27: ...27 4 Remove the stator cover Bushing...
Page 44: ...44 50Hz 220V 50Hz 240V 60Hz 220V 60Hz 240V RGX6500 7500 Electric starter model...
Page 45: ...45 50Hz 220V 50Hz 240V 60Hz 220V 60Hz 240V RGX6500 7500...
Page 46: ...46 60Hz 110 220V RGX6500 7500 Electric starter model...
Page 47: ...47 60Hz 110 220V ISSUE EMD GSxxxx Ver 1...
Page 48: ...48...