FSCurtis ICommand-Touch
V1.15
01.08.2016
46
Parameter
Values range/ Default setting/ Comments
System
types
Code
level
Recirculation
switch-on
temp.
Defines the switch-on temp. for recirculation
(compressor start without a request).
Setting range: 2°C – recirculation switch-off
temp.
Default setting: 5°C
All
Factory
Recirculation
switch-off
temp.
Defines the switch-off temp. for recirculation
(idling without a request).
Setting range: Recirculation switch-on temp. –
20°C
Default setting: 15°C
All
Factory
Ventilation
Defines whether the compressor uses 2-point
control for a fan.
Setting range: No, Yes
Default setting: No
All
Factory
Ventilation
switch-on
temp.
Defines the switch-on temp. for the fan
(programmable output).
Setting range: Ventilation switch-off temp. – 90
°C
Default setting: 65°C (Lento 15°C)
All
systems
with
activated
ventilation
Factory
Ventilation
switch-off
temp.
Defines the deactivation temperature for the fan
(programmable output).
Setting range: 0°C – ventilation switch-on
temperature
Default setting: 50°C (Lento 10°C)
All
systems
with
activated
ventilation
Factory
Dryer
Defines whether there is a dryer and whether it is
controlled (2-point control).
Setting range: No, Yes
Default setting: No (Combi T: yes)
All
Factory
Dryer switch-
on temp.
Defines the switch-on temp. for the dryer
(programmable output).
Setting range: Dryer switch-off temp. – 20 °C
Default setting: 9°C
All
systems
with
activated
dryer
Factory