FSCurtis ICommand-Touch
V1.15
01.08.2016
53
Parameter
Values range/ Default setting/ Comments
System
types
Code
level
Delayed for
water max.
Delay for the "Overfill" signal
Setting range: 0 – 100 min
Default setting: 1 min
Lento
Service
Max. time
water
discharge
Maximum time for monitoring the "Water
discharge" valve. If the water level is still too
high after this time (digital input 5 at module
addr. 6 max. water), fault message E100:
max. water level is triggered.
Setting range: 1 – 300 s
Default setting: 180 s
Lento
Service
Time for water
supply
Time for which optional "Water supply" valve
is open. Water supply output is activated
when "Min. water level" digital input is
triggered and system is loaded.
Setting range: 0 – 180 s
Default setting: 0 s
Lento
Service
Ambient
temperature
Defines whether the ambient temperature is
monitored. If "Yes", the temperature sensor is
expected at module addr. 7, analogue input 4.
Setting range: Yes /
No
Default setting: No
All
Service
Min. ambient
temperature
Defines the lower deactivation threshold for
ambient temperature. Is only displayed when
ambient temperature monitoring is activated.
Setting range: -50°C - "Max. ambient
temperature"
Default setting: -15°C
All
Service
Max. ambient
temperature:
Defines the upper deactivation threshold for
ambient temperature. Is only displayed when
ambient temperature monitoring is activated.
Setting range: "Min. ambient temperature -
100°C
Default setting: 65°C
All
Service