Lento: SCW module address 6 (MK200 8E4RA)
This module cannot be configured. The assignment of inputs/outputs is defined for Lento
systems:
Input 1 Fan 1 overcurrent
Input 2 Fan 2 overcurrent
Input 3 Converter fault
Input 4 Dryer warning
Input 5 Overfill. Maximum water level reached.
Input 6 Open water outlet
Input 7 Water filter differential pressure
Input 8 Bearing purging pressure build-up
Output 1
Bearing purging solenoid valve
Output 2
Relief valve
Output 3
PU bearing
Output 4
Outlet valve (water drain)
There are another eight inputs and four outputs per accessory module. The operator is
free to select how they are assigned. The logic can be defined for the inputs. Outputs can
be linked with one of four time frames (timer; see Section 4.4.4 ).
The following functions are available:
Digital inputs
Designation
Function
Free
Input is not evaluated
Local / remote
This input can be used to switch between local operation and
remote control.
Remote On / Off
Remote On signal via digital input (is only evaluated if
activated in the menu: see 4.2 )
Remote Load / Idling
Load request via digital input (is only evaluated if activated in
the menu: see 4.2 )
Remote basic load cycle Only relevant for basic load cycle master control. The basic
load cycle master with all connected slaves can be
activated/deactivated using this input. (Remote on/off for the
entire station)