Connection dia-
gram - 3 relays
The ripple control signal receiver and the I/Os terminal of the inverter can be connected
to one another in accordance with the connection diagram.
If the distance between the inverter and the ripple control signal receiver exceeds 10 m,
at least a CAT 5 cable is recommended and the shield must be connected at one end to
the push-in terminal of the data communication area (SHIELD).
(1)
Ripple control signal receiver with 3 relays, for effective power limiting.
(2)
I/Os of the data communication area.
Use the preconfigured file for 3-relay mode:
1
Download the file (.fpc)
2
Upload the file (.fpc) in the "I/O Power Management" menu using the "Import" button.
3
Click on the “Save” button.
The settings for 3-relay mode are stored.
97
EN
Summary of Contents for Symo GEN24 3.0
Page 2: ......
Page 11: ...General information 11...
Page 12: ...12...
Page 31: ...Backup power variant PV Point OP 31...
Page 32: ...32...
Page 34: ...34...
Page 35: ...Installation 35...
Page 36: ...36...
Page 77: ...Settings website of the inverter 77...
Page 78: ...78...
Page 104: ...104...
Page 105: ...Options 105...
Page 106: ...106...
Page 116: ...116...
Page 117: ...Appendix 117...
Page 118: ...118...
Page 132: ...132...
Page 133: ...Circuit diagrams 133...
Page 134: ...134...
Page 135: ...Circuit Diagram PV Point OP Circuit Diagram 135 EN...
Page 136: ...Fronius Symo GEN24 and BYD Battery Box Premi um HV Circuit Diagram 136...
Page 137: ...Wiring diagram surge protective device SPD Circuit Diagram 137 EN...
Page 138: ...138...
Page 139: ...Dimensions of the inverter 139...
Page 140: ...140...
Page 141: ...Fronius Symo GEN24 3 5 kW Fronius Symo GEN24 3 5 kW 141 EN...
Page 142: ...142...
Page 143: ...143 EN...
Page 144: ......