![Fronius Symo 12.0-3 208-240 Operating Instructions Manual Download Page 54](http://html1.mh-extra.com/html/fronius/symo-12-0-3-208-240/symo-12-0-3-208-240_operating-instructions-manual_2339223054.webp)
54
417
ID problem with hardware
The inverter will automati-
cally attempt to connect
again and, if possible, re-
sume feeding energy into
the grid
Update inverter firm-
ware; *)
419
Unique ID conflict
420
Communication with Hybridmanager is
not possible
421
Error HID range
425
Communication with the power module
is not possible
426–
428
Possible hardware defect
431
Software problem
Inverter does not feed ener-
gy into the grid.
Carry out AC reset
(switch automatic circuit
breaker off and on); up-
date inverter firmware; *)
436
Function incompatibility (one or more PC
boards in the inverter are not compatible
with each other, e.g., after PC board re-
placement)
The inverter will automati-
cally attempt to connect
again and, if possible, re-
sume feeding energy into
the grid
Update inverter firm-
ware; *)
437
Power module problem
438
Function incompatibility (one or more PC
boards in the inverter are not compatible
with each other, e.g., after PC board re-
placement)
The inverter will automati-
cally attempt to connect
again and, if possible, re-
sume feeding energy into
the grid
Update inverter firm-
ware; *)
443
Intermediate circuit voltage too low or
unsymmetrical
Inverter does not feed ener-
gy into the grid.
*)
445
-
Compatibility error (e.g., due to a PC
board replacement)
-
Invalid power module configuration
Inverter does not feed ener-
gy into the grid.
Update inverter firm-
ware; *)
447
Insulation fault
Inverter does not feed ener-
gy into the grid.
*)
448
Neutral conductor not connected
450
No guard found
451
Memory error detected
The inverter will automati-
cally attempt to connect
again and, if possible, re-
sume feeding energy into
the grid
*)
452
Communication error between proces-
sors
453
Grid voltage and power module do not
match
454
Grid frequency and power module do not
match
456
Anti-islanding function has stopped run-
ning properly
457
Grid relay stuck or neutral conductor
ground voltage too high
Inverter does not feed ener-
gy into the grid.
Check grounding (volt-
age of neutral conductor
ground must be under
30 V); *)
Code
Description
Behavior
Remedy