Fronius Dataman-
ager at night or
when insufficient
DC voltage is
available
The night mode parameter in the display settings in the Setup menu is preset to OFF ex-
factory.
As a result, the Fronius Datamanager is not available at night or if insufficient DC voltage
is available.
To activate the Fronius Datamanager, switch the inverter on the AC side off and back on
again and press any function key on the inverter’s display within 90 seconds.
Also refer to the “Menu items in the Setup menu”, “Display settings” (night mode) chapter.
Int./ext. power supply
-
GND
+
U
int
/U
ext
Output for internal voltage 12.8 V
or
input for external supply voltage
> 12.8 - 24 V DC (+ 20%)
Digital inputs:
0 - 3, 4 - 9
Voltage level: low = min. 0V - max. 1.8V; high = min. 3V - max. 24V DC (+ 20%)
Input currents: dependent on input voltage; input resistance = 46 kOhm
Digital outputs:
0 - 3
Switching capacity when supplied by the Fronius Datamanager 2.0 plug-in card:
3.2 W in total for all 4 digital outputs
Switching capacity when supplied by an external power supply with min. 12.8 - max.
24 V DC (+ 20%), connected to Uint/Uext and GND: 1 A, 12.8 - 24 V DC (depend-
ing on the external power supply) per digital output
The connection to the I/Os is made via the supplied mating connector.
(8)
Antenna plug
For screwing on the WLAN antenna
(9)
Modbus termination switch (for Modbus RTU)
Internal bus termination with 120-ohm resistance (yes/no)
Switch in "on” position: Termination resistance of 120 Ohm active
Switch in "off” position: No termination resistance active
IMPORTANT!
The termination resistance must be active for the first and last device
in an RS-485 bus.
(10) Fronius Solar Net master/slave switch
For switching between master and slave mode within a Fronius Solar Net ring
IMPORTANT!
All LEDs on the Fronius Datamanager 2.0 plug-in card are off in
slave mode.