37
EN-US
IMPORTANT!
The time must be set correctly in order for the USB logging function to work
properly. The time setting is handled in the ‘Setup menu items’ - ‘Time/Date’ point.
Relay (Floating
Switch Contact)
A floating switch contact (relay) on the inverter can be used to display status codes, the
inverter status (e.g. the grid power feed operation) or the Energy Manager functions.
* is only shown if the “E-Manager” function has been activated under “Relay Mode.”
Logging Interval
Activating/deactivating the USB logging function, as well as setting the logging interval
Unit
Minutes
Setting range
30 Min. / 20 Min. / 15 Min. / 10 Min. / 5 Min. / No Log
Factory setting
30 Min.
30 Min.
The logging interval is 30 minutes; new logging data is saved to
the USB thumb drive every 30 minutes.
20 Min.
15 Min.
10 Min.
5 Min.
The logging interval is 5 minutes; new logging data is saved to
the USB thumb drive every 5 minutes.
No Log
No data is saved
Setting range
Relay Mode / Relay Test / Switch-on Point* / Switch-off Point*
Relay Mode
The following functions can be displayed via the relay mode:
-
Alarm function (Permanent / ALL)
-
Active output (ON / OFF)
-
Energy Manager (E-Manager)
Setting range
ALL / Permanent / OFF / ON / E-manager
Factory setting
ALL
Alarm function:
ALL:
Switches the floating switch contact for continual and temporary ser-
vice codes (e.g. brief interruption of grid power feed operation, a ser-
vice code occurs a certain number of times per day – can be set in the
“BASIC” menu)