Ground fault indi-
cation
If a ground fault occurs in the DC cabling, the inverter disconnects from the grid.
The fault is indicated by the red ground-fault LED and the service code "434" is shown on
the display.
In this situation, the inverter is blocked from reconnection to the grid until the following ac-
tions are taken:
-
Switch the AC and DC disconnect to position “OFF“ (open-circuit)
-
Remove the ground fault in your photovoltaic system
-
Test the GFDI fuse and replace if necessary
-
Switch the AC and DC disconnect to position “ON“ (closed circuit)
Status Codes on
Fronius IG with
Several Power
Stage Sets
A special status diagnostic is run if an error occurs in an inverter with several power stage
sets.
It is also possible to call up status codes even if there is no actual error in existence. This
form of status polling may be found in the section "The Setup Menu."
Display during normal operation
When there is an error in one of the power
stage sets, the display flashes between
"STATE" and the corresponding status
code
(e.g., "STATE 515")
and
"ENTER"
-
Press the "Enter" key twice
NOTE!
When a defective fuse is changed, only replace it with a "Littlefuse KLKD
1 AMP 600V" fuse.
Summary of Contents for IG 2000
Page 2: ...0...
Page 4: ...2...
Page 6: ...4...
Page 10: ...8...
Page 15: ...General Information...
Page 16: ......
Page 21: ...Installation and Startup...
Page 22: ......
Page 50: ...48...
Page 51: ...Operation...
Page 52: ......
Page 80: ...78...
Page 81: ...Troubleshooting and Maintenance...
Page 82: ......
Page 95: ...Appendix...
Page 96: ......
Page 113: ...111 EN US...
Page 114: ...112...
Page 115: ...113 EN US...