112
775
Faulty programming of the
power stage set
1. Power stage set or filter
board not programmed
1. See device -> info menu:
look for missing versions infos
and change defective print
782* - 783*
Error during update
1. Occurs once
1. Automatically corrected
2. Recerbo defective
2. Change Recerbo
784*
Waiting on flash / busy
1. Occurs once
1. Automatically corrected
2. Recerbo defective
2. Change Recerbo
789*
Setup CRC failed
1. Wrong / defective data in
flash
1. Update software
2. Recerbo defective
2. Change Recerbo
794*
Flash data structure defect
1. Wrong / defective data in
flash
1. Update software
2. Recerbo defective
2. Change Recerbo
901
Deviation of measurement
channel 1
Current of channel 1 deviates
from the other channels
Check settings, DC fuse and
modules
902
Deviation of measurement
channel 2
Current of channel 2 deviates
from the other channels
Check settings, DC fuse and
modules
903
Deviation of measurement
channel 3
Current of channel 3 deviates
from the other channels
Check settings, DC fuse and
modules
904
Deviation of measurement
channel 4
Current of channel 4 deviates
from the other channels
Check settings, DC fuse and
modules
905
Deviation of measurement
channel 5
Current of channel 5 deviates
from the other channels
Check settings, DC fuse and
modules
990
Deviation of output from ra-
diation sensor value too big
Difference between the perfor-
mance of the irradiation sensor
and that of the inverter too big
Check archives values, shad-
ow of the modules, blown
string fuse or defect
991
Deviation of radiation sen-
sor too big
The radiation sensor deviates
too far
Check if your radiation sensor
is soiled, shaded or defect
992
No radiation sensor values
or value(s) not permitted
The radiation sensor does not
return any values or returns
values that are not permitted
Check the cable lines of the ra-
diation sensor
993
Faulty energy report
Faulty energy report due to
missing archive values
Check archive values at Froni-
us Solar.web server or Data-
logger
996
No connection to Fronius
Solar.web
No connection to Fronius So-
lar.web
1. Check LED status on Data-
logger
2. Restart Datalogger
3. Check internet connection
4. Check if customer has got
timer to switch off internet con-
nection and time interval set-
tings is too short
997
Deviation between invert-
ers
Deviation of the kWh value be-
tween inverters depending on
the settings in Fronius So-
lar.web
Check settings in system ad-
ministration in Fronius So-
lar.web (real Wpeak per
inverter and deviation), inquire
if there are shadows etc.
Code
Description
Behaviour
Remedy
Summary of Contents for 10.0-3 480
Page 2: ...2 ...
Page 5: ...Allgemeine Informationen ...
Page 6: ......
Page 13: ...Fehler Suchhilfe ...
Page 14: ......
Page 33: ...Komponenten austauschen ...
Page 34: ......
Page 40: ...40 Gewindebuchsen in der Grundscha le tauschen 1 2 3 4 5 1 2 3 4 5 ...
Page 41: ...41 DE 6 6 ...
Page 73: ...Sicherheitstechnische Überprüfung ...
Page 74: ......
Page 86: ...86 ...
Page 89: ...General information ...
Page 90: ......
Page 97: ...Error location aid ...
Page 98: ......
Page 116: ...116 ...
Page 117: ...Changing components ...
Page 118: ......
Page 124: ...124 Replacing thread ed bushings in the base shell 1 2 3 4 5 1 2 3 4 5 ...
Page 125: ...125 EN 6 6 ...
Page 156: ...156 ...
Page 157: ...Safety Inspections ...
Page 158: ......
Page 170: ...170 ...
Page 171: ...Appendix ...
Page 176: ...176 Circuit diagrams Fronius Symo ...
Page 177: ...177 Circuit diagrams Fronius 15 0 ...
Page 178: ...178 ...
Page 179: ...179 ...