Service class 7 - 10
Class 7 status codes related to control system, the configuration and inverter data record-
ing, and may directly or indirectly affect the process of feeding energy into the grid.
Code
Description
Behaviour
Remedy
701*
LN node type out of range
1. Wrong LN number
1. Insert LN number again
2. EEPROM defective
2. Change Recerbo
702*
Recerbo buffer full
1. Problems with LN ring
1. Check LN ring
2. Recerbo defective
2. Change Recerbo
703*
LN send buffer full
1. Problems with LN ring
1. Check LN ring
2. Recerbo defective
2. Change Recerbo
705*
LN number exists 2 times
1. LN number exists 2 times
1. Change LN number, LN
number must be unique
706* - 707*
Key controller communica-
tion failed
1. Occurs once
1. Automatically corrected
2. Recerbo defective
2. Change Recerbo
711*
EEPROM error
1. Recerbo defective
1. Change Recerbo
712*
Failure while writing on EE-
PROM
1. Occurs once
1. Automatically corrected
713
EEPROM data could not be
read completely
1. Occurs once
1. Automatically corrected
2. Recerbo defective
2. Change Recerbo
714* - 715*
Failure while reading from
EEPROM
1. Occurs once
1. Automatically corrected
2. Recerbo defective
2. Change Recerbo
721
Failure while writing on EE-
PROM
1. Occurs once
1. Automatically corrected
2. Recerbo defective
2. Change Recerbo
722* - 726*
Failure while reading / writ-
ing from EEPROM
1. Occurs once
1. Automatically corrected
2. Recerbo defective
2. Change Recerbo
727* - 730*
EEPROM backup defective
1. Occurs once
1. Automatically corrected
3. Recerbo defective
3. Change Recerbo
731
Failure while initialising,
USB flash drive was not de-
tected
1. USB flash drive read / write
protected
1. Remove read / write protec-
tion
2. USB flash drive not detected
2. Format USB flash drive
3. USB flash drive not support-
ed
3. Use another USB flash drive
4. Access time of the inverter
too fast
4. Update software
732
Failure while initialising,
USB flash drive has a too
high current
1. USB flash drive ineligible
due to too high current
1. Use another USB flash drive
733
No USB flash drive insert-
ed, although there should
be
1. No USB flash drive inserted
1. Insert USB flash drive
2. Unplugged USB flash drive
while updating
2. Reconnect USB flash drive
and start update again
734
Update file not identified
1. Update file has wrong format
1. Name update file correctly
(e.c. Froxxxxx.upd)
2. Update in the wrong file
2. Store update on root directo-
ry
Summary of Contents for 10.0-3 480
Page 2: ...2 ...
Page 5: ...Allgemeine Informationen ...
Page 6: ......
Page 13: ...Fehler Suchhilfe ...
Page 14: ......
Page 33: ...Komponenten austauschen ...
Page 34: ......
Page 40: ...40 Gewindebuchsen in der Grundscha le tauschen 1 2 3 4 5 1 2 3 4 5 ...
Page 41: ...41 DE 6 6 ...
Page 73: ...Sicherheitstechnische Überprüfung ...
Page 74: ......
Page 86: ...86 ...
Page 89: ...General information ...
Page 90: ......
Page 97: ...Error location aid ...
Page 98: ......
Page 116: ...116 ...
Page 117: ...Changing components ...
Page 118: ......
Page 124: ...124 Replacing thread ed bushings in the base shell 1 2 3 4 5 1 2 3 4 5 ...
Page 125: ...125 EN 6 6 ...
Page 156: ...156 ...
Page 157: ...Safety Inspections ...
Page 158: ......
Page 170: ...170 ...
Page 171: ...Appendix ...
Page 176: ...176 Circuit diagrams Fronius Symo ...
Page 177: ...177 Circuit diagrams Fronius 15 0 ...
Page 178: ...178 ...
Page 179: ...179 ...