Installation
Connecting the boiler
Page 36
M1020008_en
s
3
3.5
Connecting the thermal discharge safety device
NOTICE
The thermal discharge safety device must be connected in accordance
with ÖNORM/DIN EN 303-5 as shown in the following diagram.
The discharge safety device must be connected to a pressurised mains
water supply in such a way that it cannot be shut off.
1
Thermal discharge safety device sensor
2
Thermal discharge safety device (opens at 95 °C)
3
Safety valve
4
Cleaning valve (T-piece)
5
Check valve
6
Dirt trap
7
Pressure reducing valve
*)
*) Required when the cold water pressure is greater than 6 bar. It must be not be
possible to shut off the connection manually. Minimum cold water pressure = 2 bar
3.5.1
Installing the thermal discharge safety device sensor
U
Remove front blind plug and seal
immersion sleeve
U
Insert sensor for thermal discharge
safety device in immersion sleeve
1
2
7
6
5
4
3