Test data for operation with pellets
Description
Unit
70
85
100
Testing institute
BLT Wieselburg
Test report no.
Date of issue
1)
1)
1)
Carbon monoxide (CO)
Rated load
Partial load
mg/MJ
25.09
68.09
17.18
45.18
9.27
22.27
Nitrogen oxide (NOx)
Rated load
Partial load
mg/MJ
74.09
not measured
66.18
not measured
58.27
not measured
Organic hydrocarbons
Rated load
Partial load
mg/MJ
<1
<1
<1
<1
<1
<1
Dust
Rated load
Partial load
mg/MJ
10.27
not measured
7.55
not measured
4.82
not measured
Boiler efficiency rating
Rated load
Partial load
%
91.31
91.83
92.02
91.85
92.73
91.88
1) Values for boiler sizes 70 kW, 85 kW and 100 kW are interpolated (calculated as per EN 303-5)