4.17.2 Touchscreen - Display operating rights
System menu
Touchscreen
Display
operating rights
In this menu the operating rights for the individual room
consoles are allocated. If access from a room console to a
heating system component is permitted, then the
corresponding parameter must be set to “YES”. The number
of menus as well as the parameter entries depend on the
system configuration!
NOTICE! The operating rights of the room consoles should
be allocated from the boiler console, as unrestricted access
is only possible here.
“Touch display with address 1 – 7” and “Button display with address 1 – 7”
Heating system:
Allow access to heating circuit 01?
Allow access to heating circuit 02?
:
Allow access to heating circuit 18?
DHW tank system:
Allow access to DHW tank 01?
Allow access to DHW tank 02?
:
Allow access to DHW tank 08?
Buffer tank system:
Allow access to buffer tank 01?
:
Allow access to buffer tank 04?
Solar panel system:
Allow access to solar 01?
Heating system:
Additional freely programmable differential controller
installed
Network pump installed
Circulation pump installed
Is any secondary boiler installed? (oil, gas, wood...)
Feeder pump for distributor 1 installed
:
Feeder pump for distributor 4 installed
In the cascade, this boiler is the MASTER
Boiler:
Switch boiler on/off via room console
If this function is activated, the respective room console is
enabled for switching the boiler on and off. In order to be
able to operate the boiler, remote switching on the boiler
display must also be activated.
Parameters overview
4
Touchscreen
Service manual Lambdatronic SP 3200 for dual fuel boiler | B1460720_en