4.15 System
4.15.1 System - Settings
Setting - Boiler temperature
System menu
System
Setting
Boiler temperature
Boiler temperature setpoint
The boiler temperature is regulated to this temperature.
Setting range 70 – 90°C
Shutdown if current boiler temperature is higher than boiler
se
If the boiler temperature setpoint is exceeded by this
value, the boiler switches to “slumber” status. The boiler
starts up again below the boiler temperature setpoint.
Always shutdown when boiler maximum setpoint is
exceeded by
If the maximum boiler temperature setpoint is exceeded by
this value, the available heating circuit pumps and DHW
tank loading pumps are also activated for cooling the
boiler. If the current boiler temperature falls below the
boiler temperature setpoint, the boiler starts up again.
Minimum boiler temperature to release all pumps
When the current boiler temperature reaches this value,
the buffer loading pump is started. (Hysteresis: 2°C)
Minimum return temperature
Prerequisite: Return temperature control with mixing valve
The minimum temperature value required of the return to
the boiler.
Enable return mixer only with active storage tank pump
Prerequisite: “Variant 2 and 5” or “Variant 3”
Return mixer is controlled only when the store loading
pump is active. If the pump stops, the mixer closes the
total return / opens the bypass.
Temperature in the hi-limit stat housing at which all pumps
run
When the current temperature on the safety temperature
limiter reaches this value, the buffer loading pump is
activated and also the heating circuit pumps and boiler
loading pumps.
Start emergency skimming from STL sensor temperature
If the current temperature on the safety temperature limiter
exceeds this value, the heating circuit pumps, the DHW
tank loading pumps and the buffer tank pump are also
activated for cooling the boiler.
Heating circuit overheat invariable mode
Prerequisite: Variable mode activated or boiler system in
the cascade
The boiler setpoint temperature in heating mode is
increased by this value compared to the required flow
temperature.
Increase of temperature at sensor 1 during 5 min in status
Heating up
If the temperature does not increase at sensor 1 by the set
value at least during “Pre-Heating” status, the start
process will be cancelled and an error message will
appear on the display.