The following settings may be changed from the
Settings
page on the
Main Menu
.
▪
Mode
–
Select the desired control mode (Freeze Protection, Maintain Temperature, Always On, Always Off)
▪
Sensor
–
Select the control sensor (None, RTD, Thermistor)
▪
Sensor Location
–
Select the sensor location
(Pipe, Ambient)
▪
Setpoint
–
Select the desired temperature set point (0-300 °F)
▪
Deadband
–
Select the desired temperature dead-band (1-35 °F)
▪
Failure State
–
Select how the system should operate in the case of a sensor failure (ON, OFF)
▪
Temp. Units
–
Select the temperature units (°F, °C)
5.4.1
Advanced Settings
The following advanced settings may be changed from the
Advanced Settings
page on the
Settings
menu.
▪
Ground Fault Protection
–
The default and recommended GFEP Trip Level is 30 mA.
▪
GFEP Trip Level
–
Select the desired GFEP Trip Level (30-300 mA)
▪
Fire Protection Mode
–
Use this option to disable the GFEP circuit (NO, YES)
NOTE: IT IS NOT RECCOMENDED TO SET THE GFEP TRIP LEVEL ABOVE 30 mA.
NOTE: FIRE PROTECTION MODE DISABLES THE GFEP TRIP CIRCUIT. THIS CONFIGURATION IS NOT
RECCOMENDED AND MUST BE USED IN CONJUNCTION WITH THE DRY CONTACT ALARM SIGNAL TO ALERT
THE SYSTEM OPERATOR TO A GROUND FAULT CONDITION
▪
Network Settings
–
Adjust Network Settings
▪
Rerun BlinkUp
–
Reruns the BlinkUp process to provision the device (YES, NO)
▪
Turn of Networking
–
Disables device networking (YES, NO)
▪
Clear Network Credentials
–
Clears the device network credentials (YES, NO)
▪
Restore Default Settings
–
Reset the device to the factory default settings (Cancel, Yes)
NOTE: ALL NETWORK AND CONNECTION INFORMATION WILL BE LOST, AND THE DEVICE WILL NEED TO BE
CONFIGURED VIA BLINKUP AGAIN.
5.4.2
Alarm Settings
Alarm
settings are available under Alarms on the
Advanced Settings
menu.
▪
Latch All
–
Select this option to set all non-critical alarms to latching (NO, YES)
▪
High Current
–
Configure the high current alarm
▪
Enabled
–
Determine if the alarm is enabled (NO, YES)
▪
Threshold
–
Set the alarm threshold (0-30 A)
▪
Delay
–
Set the alarm delay (0-500 s)
NOTE: WHEN USING THE HIGH CURRENT ALARM WITH SELF-REGULATING HEAT TRACE, IT IS HIGHLY
RECOMMENDED TO USE A DELAY OF AT LEAST 300 SECONDS TO AVOID ALARMING DUE TO INRUSH
CURRENT WHEN THE HEAT TRACE IS ACTIVATED.