18 | © Frio 2021 - Rev. 0.3 - Updated 3/2/2021
4.6
S
TEP
6:
I
NTERNET
C
ONNECTION
(B
LINK
U
P
)
1.
Download and Login to the Frio App.
2.
Complete App Setup and enter all required information.
3.
Connect to the S1 Controller via BlinkUp as directed in the Frio App.
4.
Follow the in-app instructions to connect the Frio S1 controller to the internet and the Frio Cloud Platform.
4.7
S
TEP
7:
G
ROUND
F
AULT
T
EST
The Frio S1 controller includes built-in Ground Fault Equipment Protection (GFEP). The GFEP circuit must be tested
during installation. To test the GFEP circuit, follow the instructions below.
1.
Press any button on the controller to enter the
Main Menu
.
2.
Select
GFEP Test
and press enter.
3.
You will be prompted to
Test GFEP now
to test the GFEP circuit, select
Yes
.
4.
The controller will display
RUNNING GFEP TEST
during the test and
TEST SUCCESS
for a successful test. If the test
is not successful, the device will display
TEST FAILED
. If the GFEP test fails, turn off the system at the breaker and
disconnect the heat trace. Rerun the test with nothing connected to the load terminal blocks. If the test is
successful with nothing connected, there is a wiring error or a fault with the heat trace.
5.
If the test is successful with heat trace connected, record the test on the GFEP Test Form on the next page, and
ensure that the GFEP Test Form is retained by those in charge of the building's electrical installation in order to
be available to the authority having jurisdiction.