14 | © Frio 2021 - Rev. 0.3 - Updated 3/2/2021
3.7
D
EVICE
I
NFO
Device info can be viewed under
Device Info
on the
Main Menu
. Available information includes.
Device Info
Description
FW Version
Device firmware version
P/N
Device part number
S/N
Unique device serial number
Device ID
Unique device ID number
Connection
Connection type, (Wi-Fi, Cellular, Ethernet, or None if not connected )
DHCP
The DHCP server’s IP address
(Wi-Fi and Ethernet)
IP
Device IP address (Wi-Fi and Ethernet)
Network
The network the devices is currently connected to (Wi-Fi only)
rssi
Received signal strength indicator, a negative value closer to 0 shows stronger signal (Wi-Fi only)
Channel
–
The Wi-Fi channel on the router (Wi-Fi only)
Link
"10M" or "100M". Only present when link detected (Ethernet only)
3.8
S
YSTEM
R
ATINGS
Power Ratings
Supply Voltage: 120 to 277 Nominal VAC 50/60 Hz.
Single phase power only (Note: 277 VAC is phase-to-neutral in 480/277 VAC 3- phase)
Double-pole relay is safe for 240 VAC with two hot legs
Maximum Load: 30 A resistive
Wire size: 10-18 AWG
GFEP
Programable from 30 mA to 300 mA (default 30 mA)
Manual and automatic test
Fire protection mode allows user to disable GFEP
Sensor Inputs
Frio Thermistor: 2-Wire shielded pair 24 AWG leads, 10k NTC thermistor with ± 1% accuracy, operating range of -
40°C to 105°C, leads and thermistor tip are black TPE, IP68, and RoHS)
RTD: Compatible with 3-Wire pt100 RTD lead size 14-24 AWG
Low Voltage Outputs
Dry Contact Alarm: Normally Closed, Open on Alarm (contacts rated for 2 A max at 250 VAC, 14-24 AWG)
Connectivity
S1-A: WI-FI 802.11 Dual Band 2.4 GHz & 5 GHz and Ethernet (RJ45, Cat 5 or 6) See operating manual for firewall
information
S1-C: Cellular only
TIA/EIA 485 (RS-485): for BACnet MS/TP and Frio Modus (Isolated 3-wire 2 x Signal w/ GND, 14-24 AWG)
Enclosure/Environment
Enclosure tested to IP67
Operating Temperature -30 °C to 70 °C
Dimensions with mounting feet: H: 6.29 in. D: 3.625 in. W: 7.55 in.
Agency Ratings
UL 1053, CSA Standard C22.2 No. 14 (Ground-Fault Sensing and Relaying Equipment)
Complies with FCC Part 15 Subpart B