Part 4 Trouble Shooting
- 34 -
■
Outdoor Unit Error
1) 2 LED Type
LED2
(Red, 10 Digit)
LED1
(Green, 1 Digit)
Error
Code
Description
21
DC Peak (IPM Fault)
2 Times
1 Time
2 Times
1 Time
22
CT 2(Max CT)
2 Times
2 Times
2 Times
2 Times
23
DC Link Low Volt
2 Times
3 Times
2 Times
3 Times
25
Low wire volt/ high wire volt
2 Times
5 Times
2 Times
5 Times
26
DC Comp Position Error
2 Times
6 Times
2 Times
6 Times
27
PSC Fault Error
2 Times
7 Times
2 Times
7 Times
29
Inverter Compressor over-current
2 Times
9 Times
2 Times
9 Times
31
CT error (low current)
3 Times
1 Time
3 Times
1 Time
32
D-Pipe High (INV)
3 Times
2 Times
3 Times
2 Times
37
Failure Compression Ratio
3 Times
7 Times
3 Times
7 Times
40
CT Sensor (Open / Short)
4 Times
-
4 Times
-
41
INV. D-Pipe Th Error (Open / Short)
4 Times
1 Time
4 Times
1 Time
44
Outdoor Air Th Error (Open / Short)
4 Times
4 Times
4 Times
4 Times
45
Cond. Middle Pipe Error (Open / Short)
4 Times
5 Times
4 Times
5 Times
48
Cond. Out Pipe Error (Open / Short)
4 Times
8 Tiems
4 Times
8 Tiems
53
Communication Failure(Outdoor Unit
↔
Indoor Unit)
5 Times
3 Times
5 Times
3 Times
60
EEPROM Check Sum Error
6 Times
-
6 Times
-
61
Cond. Pipe High
6 Times
1 Time
6 Times
1 Time
62
Heatsink High
6 Times
2 Times
6 Times
2 Times
63
Cond. Pipe Low
6 Times
3 Times
6 Times
3 Times
65
Heatsink Th Error (Open/Short)
6 Times
5 Times
6 Times
5 Times
67
Outdoor BLDC Fan Lock
6 Times
7 Times
6 Times
7 Times
72
Failure 4Way
7 Times
2 Times
7 Times
2 Times
73
IGBT Damage
7 Times
3 Times
7 Times
3 Times
Error Indication
Indoor Unit
Outdoor Unit
LED2
LED1
Red
Green
Summary of Contents for AS - W126BMS0
Page 3: ...3 1 Safety Precautions 4 2 Nomenclature 7 Part 1 General Information...
Page 16: ...16 Part 3 Test Run 1 Check before Test Run 17 2 Test Run Flow chart 18 3 Test Run Detail 19...
Page 37: ...Part 4 Trouble Shooting 37 Troubleshooting Guide Indoor Unit...
Page 41: ...Part 4 Trouble Shooting 41 verify with hands verify with hands...
Page 46: ...Part 4 Trouble Shooting 46 3 CH23 DC Link Low Voltage Error...
Page 51: ...Part 4 Trouble Shooting 51 8 CH40 CT Sensor Error Open Short Tester Tester...
Page 53: ...Part 4 Trouble Shooting 53 10 CH53 Outdoor Unit Indoor Unit Communication Error...
Page 56: ...Part 4 Trouble Shooting 56 13 CH62 Heat Sink Overheat Error...
Page 59: ...Part 4 Trouble Shooting 59 Resistance between the lines of each 1 5 2 1 5 2 1 5 2 U V V W W U...
Page 61: ...Part 4 Trouble Shooting 61 3 CH23 DC Link Low Voltage Error...
Page 67: ...Part 4 Trouble Shooting 67 9 CH53 Outdoor Unit Indoor Unit Communication Error...
Page 68: ...Part 4 Trouble Shooting 68 10 CH60 Outdoor Unit PCB EEPROM Error...
Page 71: ...Part 4 Trouble Shooting 71 13 CH67 Outdoor BLDC Fan Lock Error...
Page 72: ...P No MFL41161608...