- 10 -
Part 2 Functions & Controls
2. Basic Mode Controls
2.1 Cooling Mode
Setting
Temp.
-0.5C(-1F)
+0.5C(1F)
Comp. OFF
Thermo ON
Thermo OFF
INV. Comp.
Frequency
Low
High
Low
High
• Operating frequency of compressor depends on the load condition, like the difference between the room temp. and
the set temp., frequency restrictions.
• If the compressor operates at some frequency, the operating frequency of compressor cannot be changed within 90
seconds. ( not emergency conditions)
• Compressor turned off when
- Intake air temperature reaches below 0.5°C(1°F) of the setting temperature for three minute continuously.
- Intake air temperature reaches below 1.5°C(3°F) of the setting temperature
• Compressors 3 minute time delay.
- After compressor off, the compressor can restart minimum 3 minute later.
2.2 Heating Mode
2˚C(3.6˚F)
4˚C(˚F)
Comp. OFF
INV. Comp.
Frequency
Low
High
Low
High
Comp. OFF
Setting
Temp.
Thermo ON
Thermo OFF
• Operating frequency of compressor depend on the load condition, The difference between the room temp. and set
temp., frequency restrictions.
• If compressor operates at some frequency, the operating frequency of compressor cannot be changed within 90 sec-
onds.
• Condition of compressor turned off
- When intake air temperature reaches 4°C(°F) above the setting temperature.
• Condition of compressor turned on
- When intake air temperature reaches below 2°C(3.6°F) of above the setting temperature.
* Condition of indoor fan turned off
• While in defrost control, the indoor and outdoor fans are turned off.
• Compressor 3 minute delay
- After compressor off, the compressor can restart minimum 3 minute later.
Summary of Contents for AS - W126BMS0
Page 3: ...3 1 Safety Precautions 4 2 Nomenclature 7 Part 1 General Information...
Page 16: ...16 Part 3 Test Run 1 Check before Test Run 17 2 Test Run Flow chart 18 3 Test Run Detail 19...
Page 37: ...Part 4 Trouble Shooting 37 Troubleshooting Guide Indoor Unit...
Page 41: ...Part 4 Trouble Shooting 41 verify with hands verify with hands...
Page 46: ...Part 4 Trouble Shooting 46 3 CH23 DC Link Low Voltage Error...
Page 51: ...Part 4 Trouble Shooting 51 8 CH40 CT Sensor Error Open Short Tester Tester...
Page 53: ...Part 4 Trouble Shooting 53 10 CH53 Outdoor Unit Indoor Unit Communication Error...
Page 56: ...Part 4 Trouble Shooting 56 13 CH62 Heat Sink Overheat Error...
Page 59: ...Part 4 Trouble Shooting 59 Resistance between the lines of each 1 5 2 1 5 2 1 5 2 U V V W W U...
Page 61: ...Part 4 Trouble Shooting 61 3 CH23 DC Link Low Voltage Error...
Page 67: ...Part 4 Trouble Shooting 67 9 CH53 Outdoor Unit Indoor Unit Communication Error...
Page 68: ...Part 4 Trouble Shooting 68 10 CH60 Outdoor Unit PCB EEPROM Error...
Page 71: ...Part 4 Trouble Shooting 71 13 CH67 Outdoor BLDC Fan Lock Error...
Page 72: ...P No MFL41161608...