- 12 -
Part 2 Functions & Controls
3. Special Mode Controls
3.1 Jet Cool operation
• In the heating mode or Auto Changeover operation, the Jet cool function does not work.
When it is input while in other mode of operation (cooling, dehumidification, Air purification, Air circulation), the Jet cool
operation takes place.
• In the Jet cool mode, the indoor fan is operated at super-high speed for 30 min. at cooling mode operation.
• In the Jet cool mode, the room temperature is maintained at a setting temperature of 18°C(64.4°F).
• When the sleep timer mode is input during the Jet cool operation, the Jet cool mode has the priority.
• When the Jet cool button is pressed, the horizontal vane of the unit is reset to those of the initial cooling mode and
then operate so that the air outflow could reach further.
3.2 Jet Heat operation
• While in cooling mode or Auto Changeover operation, the Jet Heat function does not work.
When it is input while in the Heating mode operation (dehumidification), the Jet Heat mode operation takes place
• In the Jet Heat mode, the indoor fan operated at super-high speed for 60 min. at Heating mode operation.
• In the Jet Heat mode, the room temperature is maintained at a temperature of 30°C(86°F).
• When the sleep timer mode is input during the Jet Heat mode operation, the Jet Heat mode has the priority.
• When the Jet Heat button is pressed, the horizontal vane of the unit is the unit reset to those of the initial Jet heating
mode and then operates so that the air outflow could reach under flow.
3.3 Energy saving operation in cooling mode
• During cooling and dehumidification mode of operation, the Energy saving button can be input.
• In this operation, before we feel cold the set temperature and air volume is set automatically to save energy.
Summary of Contents for AS - W126BMS0
Page 3: ...3 1 Safety Precautions 4 2 Nomenclature 7 Part 1 General Information...
Page 16: ...16 Part 3 Test Run 1 Check before Test Run 17 2 Test Run Flow chart 18 3 Test Run Detail 19...
Page 37: ...Part 4 Trouble Shooting 37 Troubleshooting Guide Indoor Unit...
Page 41: ...Part 4 Trouble Shooting 41 verify with hands verify with hands...
Page 46: ...Part 4 Trouble Shooting 46 3 CH23 DC Link Low Voltage Error...
Page 51: ...Part 4 Trouble Shooting 51 8 CH40 CT Sensor Error Open Short Tester Tester...
Page 53: ...Part 4 Trouble Shooting 53 10 CH53 Outdoor Unit Indoor Unit Communication Error...
Page 56: ...Part 4 Trouble Shooting 56 13 CH62 Heat Sink Overheat Error...
Page 59: ...Part 4 Trouble Shooting 59 Resistance between the lines of each 1 5 2 1 5 2 1 5 2 U V V W W U...
Page 61: ...Part 4 Trouble Shooting 61 3 CH23 DC Link Low Voltage Error...
Page 67: ...Part 4 Trouble Shooting 67 9 CH53 Outdoor Unit Indoor Unit Communication Error...
Page 68: ...Part 4 Trouble Shooting 68 10 CH60 Outdoor Unit PCB EEPROM Error...
Page 71: ...Part 4 Trouble Shooting 71 13 CH67 Outdoor BLDC Fan Lock Error...
Page 72: ...P No MFL41161608...