FR200F series Special Purpose Inverter
- 42 -
Ten’s place: interrupt operation,
and then start the selection
0: continue from stop
step(restart moment)
1: continue from stop step and
moment
2: re-operation starts from 0 step
Hundred’s place: Power-off
memory selection
0: power-off no memory
1: power-off memory
Thousand’s place: Simple PLC
running time
0:s (second
)
1:min (minute
)
Ten thousand’s place: Length
unit
0:0.1m
1:1m
Unit’s place: simple PLC running mode selection
0:Single-cycle, and then stops
PLC stops automatically after finishing a cycle, restart available only after receiving restart
command.
1:Single-cycle and then keep final value
PLC keeps the last speed running frequency and directions after finishing a cycle.
2:Continuous cycle
PLC automatically starts next cycle after finishing a cycle, until receiving the stop command.
Ten’s place: Interrupt operation, and then start the selection
0: continue from stop step (restart moment)
Inverter stoped, automatically record the current step, and then automatically step into this step
when restart, and continue running as the frequency specified by this step, time recalculate.
1: continue from stop step andmoment
Inverters stopped, automatically record the finished running time in current step, and then
automatically step into this step when restart, and continue to running the remained time as
frequency specified by this step.
2: re-operation starts from 0 step
Inverter restarts after stopping, running from step 0.
Hundred’s place: power-off memory selection
0: power-off no memory
Inverter no memory of PLC running status when power-off, when power-on, restart and running
from the first step.
1: power-off memory
Inverter has memory of PLC running status when power-off, include the power-off moment step
and finished running time, when power-on, continue running according to the memory data.